HRX-OM-X084
Chapter 3 Transport and Setting Up
HRR Series
3.3 Installation
3-15
3.3.6 Wiring of contact output signal
Contact output signals are the signals that output the status of this
product.
Contact specification of each signal output is shown below.
Table
3-7
Signal output contact spec. at the time of shipment
Contact output
Content of the signal
(Default setting)
Operation
Contact output signal 1
Operation status signal
output
N.O.
During operation:
Contact closed
During operation
stop:
Contact open
With power supply
cutoff:
Contact open
Contact output signal 2
Remote status signal
output
N.O.
During remote
operation:
Contact closed
During
non-remote
operation:
Contact open
With power supply
cutoff:
Contact open
Contact output signal 3
Alarm status signal
output
N.C
While alarm being
generated:
Contact open
While alarm not
being generated:
Contact closed
With power supply
shut off:
Contact open
[Tips]
This product has three output signals which can be customized depending on
the user’s application
Signals shown below can be output. Refer to Operation Manual
“Communication Function” for more details.
・
Run status signal is output
・
Remote status signal is output
・
Signal for completion of preparation (TEMP READY) is output
・
Out of temperature range status signal is output
・
Signal for operation stop alarm is output
・
Signal for continuing operation alarm is output
・
maintenance status signal is output
・
Alarm status signal is output
・
Pass through signal of contact input signal is output
・
Selected alarm status signal output
・
Signal for selection maintenance is output
Be sure to turn OFF the breaker of the facility power supply (the user's
machine power supply) before wiring.