Modbus to BACnet Start-up Guide
Page 9 of 25
6
OPERATION
6.1 Power up the device
Apply power to the device. Ensure that the power supply used complies with the specifications provided
in Section 4.2. Ensure that the cab
le is grounded using the “Frame GND” terminal. The EZ Gateway
requires a power supply that provides 9-30VDC or 12-24VAC.
6.2 Connect the PC to the EZ Gateway over the Ethernet port.
Connect an Ethernet cable between the PC and EZ Gateway or connect the EZ Gateway and the
PC to the Hub/switch using a straight Cat5 cable.
The Default IP Address of the EZ Gateway is
192.168.2.101
, Subnet Mask is
255.255.255.0.
Virus protection and firewall software should temporarily be disabled if connection problems are
experienced .
Ethernet Port
PWR+
PWR-
FG
Figure 4
– Power Connection
Figure 5
– Ethernet Port