-95-
No.EX##-OMV0017-D
6. Wireless system parameter list
- Wireless Base unit (EX600-WEN#) setting parameters
Classificat
ion
Parameter name
Set value
Initial value
Setting
when
power is off
Note
Base
setting
a)
HOLD/CLR
(unit)
CLEAR / HOLD / Software
Control
CLEAR
Available
Setting the output operation when the
fieldbus communication is
disconnected.
b) Input size
0 to 128 points (0 to 16 bytes)
Increase and decrease by 16
points (2 bytes).
128 points /
16 byte
Available
c)
Output size
(includes
valves)
0 to 128 points (0 to 16 bytes)
Increase and decrease by 16
points (2 bytes).
128 points /
16 byte
Available
d)
in which
includes a
valve density
of
0 to 32 points (0 to 4 bytes)
Increase and decrease by 8
points (1 byte).
32 points /
4 byte
Available
The valve manifold output points are
included in the module output points.
The number of effective points are
limited to within the setting range of
the module output points.
e)
Wireless
signal
Active / Idle
Active
Available
If set to "Idle", the wireless
communication is disconnected.
f)
Unit address
order
Mode 1 / Mode 2
Mode 1
Available
Mode 1:
Allocation to the right from the end
plate.
Mode 2:
Allocation to the left from the wireless
unit.
Ethernet
setting
a)
IP address
type
Manual
/
DHCP
/
Remote
Control
Manual
Available
The IP address can be input manually
only when "Manual" mode is selected.
b)
Auto
MDI/MDI-X
Auto / MDI / MDI-X
Auto
Available
c) Duplex
Full Duplex / Half Duplex
Full Duplex
Available
d) Speed
Auto / 100 Mbps / 10 Mbps
Auto
Available
System
setting
a) I/O mapping
Manual
Manual
Available
When the total size (byte) of the I/O
mapping is an odd number, 1 byte will
be added automatically so that an
even number will be allocated.
b)
System input
size
16, 128 to 1280 points (2, 16
to 160 bytes)
Increase and decrease by 128
points.
1280 points /
160 byte
Available
This is not settable when the I/O
mapping is set to "Auto".
c)
System
output size
16, 128 to 1280 points (2, 16
to 160 bytes)
Increase and decrease by 128
points.
1280 points /
160 byte
Available
This is not settable when the I/O
mapping is set to "Auto".
d)
Diagnostic
allocation
None / Simple / Advanced
Advanced
Available
Diagnostic information is allocated to
the head of the input data of the I/O
map.
e)
Max. Remote
units
0 / 15 / 31 / 63 / 127 Remotes 15 Remotes
Available
Wireless channels for the number of
the set units are enabled.
f)
DA refresh
time (sec)
0.1 / 0.2 / 0.5 / 1 / 2 / 5 / 10 /
30 / 60 s
1 s
Available
Set the sampling frequency of the
analog output equipment.