19
18
Wiring (continued)
A. For dual power
supply use
B. For single power
supply use
24 VDC
24 VDC
24 VDC
Display/ Switch Setting
SW1
OFF
ON
OFF
ON
COM C COM D
COM A COM B
SW2
L RUN L ERR
PWR(V) PWR
INPUT
Setting for Display
Display
Meaning
PWR
(V)
The power for output is supplied at specified voltage: Lights up
The power for output is not supplied at specified voltage: Goes off
PWR
The power for input and GW unit controlling part is supplied: Lights up
The power for input and GW unit controlling part is not supplied: Goes off
L RUN
Normally communication: Lights up
Communication interrupted: Goes off
L ERR
Communication error: Lights up
Setting of station number and of transmitting speed setting
switch is changed during powered: Lights up
(Blink with 0.4 s interval)
Normally communicating: Goes off
COM A
COM A is receiving data: Lights up
∗
COM A is having no data to receive: Goes off
COM B
COM B is receiving data: Lights up
∗
COM B is having no data to receive: Goes off
COM C
COM C is receiving data: Lights up
∗
COM C is having no data to receive: Goes off
COM D
COM D is receiving data: Lights up
∗
COM D is having no data to receive: Goes off
∗
: It is lit when input unit is connected and communicating normally.
Power supply wiring
Connect power supply wiring to the two power supply 2-pin
connectors. Power supply structure consists of 2 systems, but it
can be used with both single power supply and separate power
supply.
Individual power supply for other units is not necessary.
Make sure of connection with the designated pin. Tighten the
connector securely to 0.5 to 0.6 Nm tightening torque.
Power supply connector
Power supply
for output
Power supply
for input and
controlling GW
Power supply connector
PWR
(V)
PWR
0 V
24 V
24 V
0 V
Note:
A secure earth connection (Protection class 3) should be
performed for FG terminal.
(SLD, FG and FG terminal in communication connector for
CC-Link are connected inside of GW unit.)