SMC Networks EX500-GDN1 Installation & Maintenance Manual Download Page 1

Installation & Maintenance Manual

Reduced wiring system
DeviceNet Compatible GW Unit

EX500-GDN1

Specification

Follow the instructions given below when handling your
reduced wiring system. Otherwise a damage or failure to
cause a malfunction can result.

Operate the reduced wiring system at the specified voltage.
Reserve space for maintenance.
Do not remove any name plate or label.
Do not drop, hit or apply an excessive shock to the unit.
Follow the specified tightening torque.

Indicates a potentially hazardous situation that
could result in death or severe injury if you do
not follow instructions.

Read this manual and follow its instructions. Signal words such as
WARNING, CAUTION and NOTE will be followed by important safety
information that must be carefully reviewed.

Gives you helpful information.

IMPORTANT MESSAGES

The body of unit and this manual contain the essential information for the
protection of users and others from possible injury and property damage
and to ensure correct handling.
Please check that you fully understand the definitions of the following
messages ( symbols ) before going on to read the body of this manual,
and always follow the instructions.
Please also read the instruction manuals etc. of related machines and
understand the contents before use.

Do not disassemble,
modify ( including modification of printed circuit board ) or
repair.

Otherwise injury or failure can result.

Do not operate beyond specification range.

Otherwise fire, malfunction or damage to the reduced wiring system can
result.
Confirm the specifications before operation.

Do not operate in atmosphere of
flammable/explosive/corrosive gas.

Otherwise fire, explosion or corrosion can result.
This reduced wiring system is not explosion-proof type.

Indicates a potentially hazardous situation
that, if not avoided, may result in minor injury
or moderate injury.

For use in interlock circuit:
Provide double interlock system by adding different type of
protection

( such as mechanical protection ).

Check that the interlock circuit is working normally.

Otherwise accident caused by malfunction can result.

Before performing maintenance:

Turn off power supply.
Stop air supply, exhaust compressed air in piping, and
confirm the release to atmosphere.

Otherwise injury can result.

Conduct proper functional inspection after completing
maintenance.

In the case of abnormality such as unit does not work normally, stop the
operation. Otherwise safety cannot be assured due to unintended
malfunction.

Provide grounding to improve safety and noise resistance
of reduced wiring system.

Provide grounding as close to the unit as possible to shorten distance for
grounding.

NOTE

Handling precautions

Use the following UL-recognized DC power supply to combine with.

1. UL508-compatible limited voltage/current circuit

A circuit using the secondary coil of an insulating transformer that
meets following conditions as power source.

Maximum voltage ( at no load )

: 30Vrms ( 42.4Vpeak ) or below

Maximum current:

( 1 ) 8A or less ( including when

short-circuited )

( 2 ) When limited by the circuit

protector ( such as fuse )
having the following rating.

2. UL1310-compatible Class 2 power supply unit or circuit of max.

30Vrms ( 42.4Vpeak ) or less using a UL1585-compatible Class 2
transformer as power source. ( Class 2 circuit )

Do not apply any excessive force to cables by repeated bending,
tensioning or placing a heavy object on the cables.
Connect wires and cables correctly.
Do not perform any wiring work while the power is on.
Do not use the reduced wiring system on the same wiring route as the
power line or high voltage line.
Confirm the insulation of wiring.
Perform the power supply wiring by dividing into two lines ---- one is for
power supply for output and the other is for power supply for input and
controlling GW/SI.
Take sufficient measures against noise such as noise filter when
incorporating the reduced wiring system into a machine or equipment.
Mount a terminal plug or a waterproof cap on each unused M12
connector for input/output

( communication connector, communication ports A - D, and power

supply for input and controlling GW/SI ).

Take sufficient shielding measures when operating the product in any
of the following places.

( 1 ) A place where noise due to static electricity etc. is generated
( 2 ) A place of high electric field strength
( 3 ) A place where exposure to radioactivity is possible
( 4 ) A place near power cable

Do not operate the product in a place where there is a source of surge.
Use a surge absorbing element built-in type to directly drive the load
that generates surge voltage such as solenoid valve.
Prevent any foreign matter such as remnant of wires from getting
inside the product when opening the station number switch protective
cover.
Install the reduced wiring system in a place free from vibration and
impact.
Operate the product in the specified ambient temperature range.
Do not use in a place to be affected by the radiant heat from a
surrounding heat source.
Set the DIP switch and rotary switch by using a sharp-pointed
watchmakers screwdriver etc.
Perform the maintenance regularly.
Conduct an appropriate functional inspection after completing the
maintenance.
Do not use chemicals such as benzin and thinner to clean the product.

Basic specifications

Rated voltage

24VDC

Range of power
supply voltage

Power supply for input and controlling GW/SI: 24VDC

10%

Power supply for output: 24VDC+10%/-5% ( Voltage
drop warning at around 20V )

Rated current

Power supply for input and controlling GW/SI: Max. 3.0A

Inside GW unit: 0.2A
Input device and SI control section: 2.8A

Power supply for solenoid valves and output: Max. 3.0A

Number of input/
output points

Input point: Max. 64/Output point: Max. 64

Higher-level bus

Protocol

DeviceNet Release 2.0

Slave ( slave station ) type

MAC ID setting range

Group2 only server

0 - 63

Device information

Applicable message

I/O message size

Data rate

Vender code:7 ( SMC Corp. )
Product type:12 ( communication adapter )
Product code:5001

Duplicate MAC ID check message
Group2 only unconnected explicit message
Explicit message
Poll I/O message

Input:8 bytes
Output:8 bytes

125kbps, 250kbps, 500kbps

Insulation method

Photocoupler

(

)

Outline with Dimensions

(

in mm

)

E

X

5

0

0

-G
D

N

1

24VDC

COM A

COM B

COM C

COM D

BUS

MS

NS

SOL

8

8

1

0

4

6

4

8

.8

136

160

GATEWAY UNIT

EX500 SERIES

P

E

EX500 body

Lower-level bus

Number of branches for
input/output

4 branches ( 16 points/branch ) for input
4 branches ( 16 points/branch ) for output

Communication method

Protocol: Dedicated for SMC
Speed:

750kbps

Branch current for input
( Note )

Max. 0.5 [A] per branch ( when SI unit and
input devices are connected )

Branch current for output

Max. 0.65 [A] per branch
( when SI unit EX500-S

01 is connected )

Max. 0.75 [A] per branch ( when SI unit
EX500-Q

is connected )

Branch cable length

5m or less between connect units.
( total extended length per branch: 10m or less )

Note: Total value of maximum current consumption and maximum load

current of input devices to connect.

Names and Functions of individual parts

MS

NS

SOL

BUS

EX5

00-

GD

N1

Communication
connector

1

2

3

4

5

6

7

8

Note1: For wiring method, refer to subsection "Wiring" in this manual.
Note2: For display and setting method, refer to subsection "Switch Setting" and

"Display" in this manual.

Power supply
connector

Communication port A
( COM A )

Communication port B
( COM B )

Communication port C
( COM C )

Communication port D
( COM D )

Display

Connect with DeviceNet line. ( Note 1 )

Name

No

.

Application

Supply power for output devices such as solenoid
valve, for input devices such as sensor, and for
controlling GW/SI by using power supply
connector cable. ( Note1 )

Display the power supply status and
communication status with PLC. ( Note2 )

Station number switch
protective cover

Set address and data rate by using the
switches under this cover. ( Note2 )

Connect SI unit ( manifold valve ) or Input unit
by using branch cable with M12 connectors.
( Note1 )

Safety Instructions (continue)

Safety Instructions

Installation ( unit : mm )

Cutout Dimensions for Mounting ( Tolerance :   0.2 )

148

6

8

5

4 M5

Screw mounting

Secure at four positions with screws with head diameter of 5.2 or
more and thread length of 15mm or more.

EX500-TFI66GB-A

No Load Voltage (Vpeak)

Max. Current Rating (A)

0 to 20 [V]

5.0

20 [V] to 30 [V]

100/peak voltage