Installation & Maintenance Manual
Fieldbus device (SI unit)
EX260 Series for DeviceNet

TM

EX260-TFN21

Safety Instructions

This manual contains essential information for the protection of users
and others from possible injury and/or equipment damage.
•Read this manual before using the product, to ensure correct handling,

and read the manuals of related apparatus before use.

•Keep this manual in a safe place for future reference.
•These instructions indicate the level of potential hazard with the labels

of "Caution", "Warning" or "Danger", followed by important safety
information which must be carefully followed.

•To ensure safety of personnel and equipment the safety instructions in

this manual and the product catalogue must be observed, along with
other relevant safety practices.

WARNING indicates a hazard with a medium level
of risk which, if not avoided, could result in death or
serious injury.

DANGER indicates a hazard with a high level of risk
which, if not avoided, will result in death or serious
injury.

CAUTION indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury.

Caution

Warning

Danger

Summary of Product element

This product is class A equipment that is intended for use in an industrial
environment.
There may be potential difficulties in ensuring electromagnetic
compatibility in other environments due to conducted as well as radiated
disturbances.

NOTE

When conformity to UL is necessary the SI unit must be used with a
UL 1310 Class2 power supply.

<EX260-SDN1/-SDN2/-SDN3/-SDN4>

1

3

4

2

5

6

7

Fieldbus interface
connector (BUS OUT)

Element

Description

DeviceNet

TM

connection

(M12 5-pole socket, A-coded)

Fieldbus interface
connector (BUS IN)

DeviceNet

TM

connection

(M12 5-pole plug, A-coded)

Ground terminal

Functional earth (M3 screw)

Output connector

Output signal interface for valve manifold

1

No.

2

4
5

2 pcs. M3x30 screw for connection to the valve
manifold

Seal cap

1 pc. seal cap for unused fieldbus interface
connector (BUS OUT)

Accessories

LED and switch

Bus status−specific and SI unit−specific LEDs
Switches for setting of node address and
operating mode

Mounting hole

Mounting hole for connection to the valve manifold

6

7

Power supply
connector

Power supply with load voltage for valves
(M12 4-pole plug, A-coded)

3

Hexagon socket head cap
screw

•Do not disassemble, modify (including changing the printed circuit

board) or repair.

An injury or failure can result.

•Do not operate the product outside of the specifications.

Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.

•Do not operate in an atmosphere containing flammable or

explosive gases.

Fire or an explosion can result.
This product is not designed to be explosion proof.

•If using the product in an interlocking circuit:

Provide a double interlocking system, for example a mechanical
system.

Check the product regularly for proper operation.

Otherwise malfunction can result, causing an accident.

•The following instructions must be followed during maintenance:

Turn off the power supply.

Stop the air supply, exhaust the residual pressure and verify that the
air is released before performing maintenance.

Otherwise an injury can result.

•After maintenance is complete, perform appropriate functional

inspections.

Stop operation if the equipment does not function properly.
Safety cannot be assured in the case of unexpected malfunction.

•Provide grounding to assure the safety and noise resistance of the

Fieldbus system.

Individual grounding should be provided close to the product with a
short cable.

Installation

General instructions on installation and maintenance

Connect valve manifold to the SI unit.
Connectable valve manifolds are the same as for EX250 series SI unit.
Refer to the EX250 series valve manifold section in the valve catalogue
for valve manifold dimensions.

M3 hexagon screw

Tightening torque 0.6 Nm

Valve manifold

: Thread size: M3×30

Replacement of the SI unit
•Remove the M3 hexagon screws from the SI unit and release the

SI unit from the valve manifold.

•Replace the SI unit.
•Tighten the screws with the specified tightening torque. (0.6 Nm)

Precautions for maintenance
•Be sure to switch off the power.
•Check there is no foreign matter inside the SI unit.
•Check there is no damage and no foreign matter being stuck to the

gasket.

•Be sure to tighten the screws with the specified torque.

If the SI unit is not assembled properly, inside PCBs may be damaged or
liquid and/or dust may enter into the unit.

Assembly and disassembly of the SI unit

Installation (Continued)

Connecting cables

Select the appropriate cables to mate with the connectors mounted on the
SI unit.

Fieldbus interface connector layout

Warning

Caution

BUS OUT: M12  5-pole socket A-coded

DRAIN

Designation

Contact layout

BUS IN

V+

V-

CAN_L

1

No.

2
3

5

CAN_H

4

2

5

4

3

1

1

5

4

3

2

BUS OUT

BUS IN: M12  5-pole plug A-coded

Note: To avoid causing disruption of “downstream” devices whilst

replacing SI unit, use a DeviceNet

TM

tap rather than making

connections to the BUS OUT connector.

Power supply connector layout

Ground terminal

Connect the ground terminal to ground.
Resistance to ground should be 100 ohms or less.

Designation

Contact layout

+24 V for solenoid valve

1

No.

2
3

0 V for solenoid valve

4

1

3

4

2

PWR: M12  4-pole plug A-coded

Switch setting

Set the DeviceNet

TM 

node address (MAC ID), DeviceNet

TM

communication

speed and fail safe mode of the SI unit using the 10-element switch.

Communication speed

Address

HW/SW

HOLD/CLEAR

9 10

7 8

5 6

3 4

1 2

ON

Setting

Note: Be sure to switch off the power supply before setting the switches.

MAC ID

Switch No.

No.6

No.5

No.8

No.7

No.10

No.9

Address setting (switch No. 5 to 10)

The DeviceNet

TM

address (MAC ID) is binary coded and can be set from

0 to 63

Note: Factory default setting is 63.

16

32

4

8

1

2

0

0

0

0

0

0

0

0

0

0

0

1

0

1

0

0

0

0

0

1

2

:

:

:

:

:

:

:

1

1

1

1

0

1

62

1

1

1

1

1

1

63

0: OFF, 1: ON

Setting (Continued)

Communication speed setting (switch No. 3 to 4)

The DeviceNet

TM

communication speed is binary coded and can be

set to 125 kbps, 250 kbps and 500 kbps.

Note: Factory default setting is 125 kbps.

Communication
speed

Switch No.

No.4

No.3

0

0

1

0

250 kbps

0

1

500 kbps

1

1

-

0: OFF, 1: ON

125 kbps

Note: Each output can be set individually over the network.

HOLD/CLEAR setting (switch No.2)

Set the reaction of outputs to the communication error
(All outputs will be set under the same conditions)

Note: Factory default setting is CLEAR.

HOLD/CLEAR

Switch No.

Description

No.2

0

Hold the last state before
communication error

1

HOLD

CLEAR

Clear all outputs

0: OFF, 1: ON

HW/SW mode setting (switch No.1)

Modifications to the address and speed can be made locally or over
the network.
Local setting: Hardware mode (Hereinafter referred to as “HW mode”)
Network setting: Software mode (Hereinafter referred to as “SW mode”)

Note: Factory default setting is "HW mode".

HW/SW

Switch No.

Description

No.1

0

Set the address and speed over the
DeviceNet

TM

network

(Switch setting is invalid)

1

SW

HW

Set the address and speed locally using the
SI unit switches

0: OFF, 1: ON

Output number assignment

The output number refers to the solenoid position on the manifold and
starts at zero.

Bit: 7

0

Bit: 7

0

Bit: 7

0

Bit: 7

0

0

1

2 4 6

3 5 7

8

9

16

17

30

31

28

29

6

4

・・・

・・・

・・

・・・

・・

・・

6

4

1 3 5 7 1

1

5 7

Output No.

Output No.

Bit No.

Bit No.

Valve manifold

Solenoid on side A

Solenoid on side B

Side D

0: Solenoid valve: OFF

1: Solenoid valve: ON

 Byte

 0 Offset
 Byte

 1 Offset
 Byte

 2 Offset
 Byte

 3 Offset

(SI unit side)

2

0

0

0

16 outputs

type

32 outputs

type

Setting over the DeviceNet

TM

network

Technical documentation giving detailed information about setting
the unit over the DeviceNet

TM

network can be found on the SMC

website (URL http://www.smcworld.com)

Diagnostic information

Technical documentation giving detailed diagnostic information can
be found on the SMC website (URL http://www.smcworld.com)

Reviews: