No.D-
※
S-OMJ0002
Trouble
No.
Trouble
phenomenon
Possible cause
of trouble
Check point
Trouble shooting
Set position
displacement
Looseness of switch mounting screw
Fix at the right position with right
torque
Tightening torque : 0.5 to 0.9N
•
m
Wiring failure
Condition of connecting part
(connector contact pin crimp
terminal)
Correct wiring
(Re-wiring of connecting part)
Lead wire
disconnection
Presence of repeated bending stress
to one point of the lead wire
(Bend radius/ Tensile force to lead
wire)
Replace the switch
(Correct tensile force/ increase bend
radius)
6
Unstable operation
(Chattering)
Malfunction due
to turbulence
magnetic field
Presence of magnetic field
generating source around the
cylinder
(Cylinder , electric welding machine
conductor, motor, magnet etc.)
Keep the cylinder away from
magnetic field generating source