-9- 

 

No.D-

S-OMI0002-B 

Solid state Auto switch 

Design and Selection 

Caution 

(1) Wiring should be kept as short as possible. 

Do not use a cable longer than 100 m. 
For long wire lengths, we recommend a ferrite core should be attached to both ends of the cable, to reduce noise. 

(2) Do not use a load which generates a surge voltage. 

When a load which generates a surge voltage is to be directly driven, operate such as a relay or solenoid, use an auto 
switch with built-in surge protection. 

(3) Pay attention to the internal voltage drop of the switch. 

In general, the internal voltage drop will be greater with a 2-wire solid state auto switch than with a reed type auto 
switch. 
When auto switches are connected in series, the voltage drop will be "n" times larger when "n" auto switches are 
connected. 
Even though an auto switch may operate normally, the load may not operate. 
Note that a 12 VDC relay is not applicable. 

(4) Pay attention to the leakage current. 

<2-wire type> 
With a 2 wire solid state auto switch, current (leakage current) flows to the load to operate the internal circuit even 
when the switch is in the OFF state. 

Current to operate load (OFF condition) > Leakage current 

If the criteria given in the above formula are not met, the auto switch will not reset correctly (stays ON). 
Use a 3 wire type auto switch if this specification cannot be satisfied. 
In addition, leakage current flow to the load will be "n" times larger when "n" auto switches are connected in parallel. 

(5) The solid state auto switch output will be unstable for 50 ms after power is supplied. 

During the time after supplying power, the input device (e.g. PLC, relay) may consider the ON position as OFF output 
or the OFF position as ON output. 
Please set up the application to consider the signals will be invalid within 50 ms after power is supplied. 
Perform a similar setting when using the SMC AHC system (Auto Hand Changing system) MA series.

 

 
 

Wiring 

Caution 

(1) Do not short-circuit the load. 

The auto switch will be damaged if the load is short-circuited. 

(2) Avoid incorrect wiring. 

1) If connections are reversed on a 2-wire type auto switch, the switch will not be damaged if protected by a protection 

circuit, but the switch will always stay in an ON state. 

However, it is still necessary to avoid reversed connections, since the switch could be damaged by a load short 
circuit in this condition. 

2) If connections are reversed (power supply wire + and -) on a 3-wire type auto switch, the switch will be protected by 

a protection circuit. However, if the blue wire is connected to the power supply (+) and the black wire is connected 
to the power supply (-), the auto switch will be damaged. 

(3) Please note the correct stripping direction when removing the cable sheath. The insulator may be split or 

damaged depending on the direction used.

 

 

Recommended tool:

 

Description 

Part number 

Wire stripper 

D-M9N-SWY 

 

 

: For 2-wire type auto switches, a round wire stripper (

2.0) can be used.

 

Summary of Contents for D-F6# Series

Page 1: ...No D S OMI0002 B PRODUCT NAME Solid state auto switch MODEL Series Product Number D F6 Series ...

Page 2: ...tions 2 Model Indication and How to Order 11 Summary of Product parts 11 Definition and terminology 12 Mounting and Installation 13 Installation 13 Circuit diagram 14 Troubleshooting 15 Specifications 19 Specifications 19 Dimensions 20 Operating range 21 ...

Page 3: ... of equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to r...

Page 4: ...lity a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalogue for the particular products 2 Vacuum pads are excluded from this 1 year warra...

Page 5: ...rmful fluids Fire malfunction or damage to the product can result Verify the specifications before use Do not operate in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof Do not use the product in a place where static electricity is a problem Otherwise it can cause failure or malfunction of the system If using t...

Page 6: ...erform appropriate functional inspections and leak tests Stop operation if the equipment does not function properly Safety cannot be assured in the case of unexpected malfunction Be sure to confirm the wiring condition This series including this product is not equipped with excessive current protection Therefore incorrect wiring and or a short circuited load could damage and or burn this product ...

Page 7: ...ce of at least 40 mm If the separation distance is specified for the actuator series then use that value The auto switches may malfunction due to magnetic field interference Use of a magnetic screen plate MU S025 or commercially available magnetic screening tape can reduce the interference of magnetic fields 3 Provide sufficient space for maintenance When designing an application allow sufficient ...

Page 8: ...n at the end of stroke Some actuator and cylinder series have their own setting methods In such cases follow the instructions given 6 Check and adjust the actual auto switch operation during installation The auto switch may not operate in the correct actuator mounting position due to the installation environment Also check and adjust the auto switch operation when used in intermediate stroke posit...

Page 9: ...e elasticity of lead wires applications in welding sites etc 7 Do not use in direct sunlight 8 Do not mount the auto switch in locations where it is exposed to radiant heat 9 The auto switch is CE marked but not immune to lightning strikes Take measures against lightning strikes in the system Maintenance Warning 1 Removal of equipment and exhausting the compressed air When equipment is to be remov...

Page 10: ...n leakage current flow to the load will be n times larger when n auto switches are connected in parallel 5 The solid state auto switch output will be unstable for 50 ms after power is supplied During the time after supplying power the input device e g PLC relay may consider the ON position as OFF output or the OFF position as ON output Please set up the application to consider the signals will be ...

Page 11: ...cation where surges are generated When there are units solenoid lifter high frequency induction furnace motor etc which generate a large amount of surge in the area around the actuator with solid state auto switches this may cause damage to the auto switch internal circuit ...

Page 12: ... D S OMI0002 B Model Indication and How to Order D F6 Output type Lead wire length Symbol Content Symbol Content N 3 wire NPN output Nil 0 5 m P 3 wire PNP output L 3 m B 2 wire Z 5 m Summary of Product parts ...

Page 13: ...en the switch is turned on Most sensitive position Indicates the center position of the sensor most sensitive and becomes the center of operating range Auto switch which absorb current from the signal line during ON status NPN OUTPUT Auto switch which output current from the signal line during ON status PNP OUTPUT Reed type auto switch Auto switch to output ON OFF by mechanical contact Sequence co...

Page 14: ...equired tightening torque of the set screw width across flats 3 mm is 0 8 to 1 4 Nm The followings are the recommended tools Description Part number Screw mounting jig D F6B 650 Setting the detecting position Set the actuator at the stroke end Set the switch in the area to where the auto switch red lamp light Detecting actuator end Based on A and B dimensions in the actuator catalogue set the swit...

Page 15: ... 14 No D S OMI0002 B Circuit diagram D F6N D F6P D F6B Sink input mode D F6B Source input mode ...

Page 16: ...SMC Switch output stays OFF Applicable actuator Switch failure Switch failure Wrong selection Refer to reference No 4 Normal Switch failure Select 50 types Refer to reference No 6 Indicator light stays OFF Indicator light stays ON Refer to reference No 1 Detection incorrect Switch output stays ON Refer to reference No 2 Refer to reference No 3 Switch output operate correctly Normal Indicator light...

Page 17: ...lure 2 wire type Check if the switch wiring connection is reversed Brown Blue Correct wiring Refer to Circuit diagram on page 14 2 Output stays ON Display stays OFF Switch failure 3 wire type Replace the switch Not match with load specification 2 wire type Check if load specification satisfy the formula below Load ON voltage Switch leak current x n x Load resistance or load OFF current Switch leak...

Page 18: ... 0 8 to 1 4 Nm Stop position displacement of the piston Check if the stroke stop position is Inconsistent Stabilize stop position Correction of displacement cushion Presence of magnetic field generating source around the cylinder Electric welding machine conductor Strong magnet Use the shield between magnetic field generating source and cylinder Influence of magnetic field of adjacent cylinder 20 ...

Page 19: ...acket or set screw Fix at the right position with right torque Tightening torque 0 8 to 1 4 Nm Wiring failure Condition of connecting part connector contact pin crimp terminal Correct wiring Re wiring of connecting part Lead wire disconnection Presence of repeated bending stress to one point of the lead wire Bend radius Tensile force to lead wire Correct wiring Correct tensile force increase bend ...

Page 20: ...ternal voltage drop 0 8 V or less at 10 mA load current 2 V or less at 40 mA load current 4 V or less Leakage current 100 A or less at 24 VDC 0 8 mA or less Operating time 1 ms or less Indicator light Operation range red LED Electrical entry type Grommet Lead wire Oilproof heavy duty vinyl cord 2 7 x 3 2 oval 0 15 mm2 2 wire D F6B 3 wire D F6N D F6P Insulation resistance 50 M or more under the tes...

Page 21: ... 20 No D S OMI0002 B Dimensions ...

Page 22: ...eter Series Section 20 25 32 40 50 63 HYQ Operating range 8 7 5 9 8 5 8 5 9 HYC Operating range 9 8 5 9 9 HYG Operating range 8 7 5 9 8 5 8 5 9 It is not for guarantee but measure including hysteresis Dispersion is approx 50 It might be changed drastically depending on the ambient ...

Page 23: ...vision history A Special tools were added page 13 B Revision Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2004 2012 SMC Corporation All Rights Reserved ...

Reviews: