1. Actuator drive

When a component such as a solenoid valve or actuator is to 
be driven using this product, take appropriate measures to pre-
vent potential danger caused by actuator operation.

2. Holding of pressure

Since the products are subject to air leakage (allowed), they 
cannot be used for applications such as holding pressure in a 
pressure vessel.

3. Maintenance space

The installation should allow sufficient space for maintenance 
activities.

Selection

Design

Warning

1. Leakage voltage

Particularly when using a C-R element (surge voltage suppres-
sor) for protection of the switching element, take note that lea-
kage voltage will increase due to leakage current flowing 
through the C-R element, etc.

2. Low temperature operation

Although the valve can be operated at a temperature as low as 
0

°

C, measures should be taken to avoid solidification or free-

zing of drainage and moisture, etc.

Caution

AC coil is 20% or less of rated voltage.

DC coil is 3% or less of rated voltage.

Switching element

Resistor

OFF

Leakage current

Valve

Power 
supply

1. Confirm the specifications.

The products presented in this catalog are designed only for 
use in compressed air systems. Do not operate at pressures or 
temperatures, etc., beyond the range of specifications, as this 
can cause damage or malfunction.
(Refer to specifications.)
Contact SMC when using a fluid other than compressed air.

2. Extended periods of continuous energization

Contact SMC if valves will be continuously energized for 
extended periods of time.

3. Operation of closed centre solenoid valves

When closed center solenoid valves are used, or when used on 
an actuator with a load factor of 50% or more, jumping 
(lurching) cannot be prevented even if this product is used.

4. Using a regulator on the secondary side

When mounting a regulator on the secondary side (A port side), 
use a residual pressure relief regulator (AR2550 to 4050) or a 
check type regulator (AR2560 to 6060).

With a standard regulator (AR1000 to 6000), the secondary 
side pressure may not be released when this valve is 
exhausted.

5. Operation of secondary side solenoid valves 

To operate solenoid valves mounted on this product's 
secondary side (A port side), first confirm that the secondary 
side's pressure (P) has increased to become equal to the 
primary side's pressure (P).

6. Operation

The residual pressure release function of this product is for 
emergency use only; therefore, avoid operation in the same 
manner as ordinary 3 port valves.

7. Using a lubricator

If mounting a lubricator, mount it on the primary side (P port 
side), of this product. If mounted on the secondary side (A port 
side), back flow of oil will occur and may spurt out of the valve's 
R port.

8. Operation for air blowing

This product cannot be operated for air blowing due to the me-
chanism that switches the main valve to be fully open after the 
secondary side's pressure increases to approximately 1/2 of the 
primary side.

Selection

Warning

1. If air leakage increases or equipment does 

not operate properly, stop operation.

After mounting or maintenance, etc., connect the compressed 
air and power supplies, and perform appropriate function and 
leakage tests to confirm that the unit is mounted properly.

2. Instruction manual

Mount and operate the product after reading the manual care-
fully and understanding its contents. Also keep the manual 
where it can be referred to as necessary.

3. Painting and coating

Warnings or specifications printed or pasted on the product 
should not be erased, removed or covered up.
Furthermore, contact SMC before paining resin parts, as this 
may cause adverse effects depending on the solvent.

Mounting

Warning

1. To perform the initial speed adjustment of a 

secondary side actuator, supply air from this 
valve's primary side and turn ON the pilot 
valve. Then, rotate the needle counter clock-
wise from the fully closed condition.

Adjustment

Caution

Leakage

voltage

AV2000/3000/4000/5000

Specific Product Precautions 1

Be sure to read before handling.
Refer to page 7 for safety instructions.

8

Summary of Contents for AV2000

Page 1: ...8 G1 2 G3 4 G1 1 5 0 2 1 0 G1 8 0 60 21 1150 39 6 2150 64 8 3500 113 6150 122 6650 A R 25 52 80 8 132 141 0 27 0 48 0 74 1 6 1 54 220 VAC 24 VDC 15 10 1 8 5 6 3 4 IP65 2 1 2 3 4 5 NBR 6 NBR 7 NBR 8 N...

Page 2: ...0 AN200 02 AN300 03 AN400 04 AN500 06 AN600 10 X31 X32 X30 KT AV2000 KT AV3000 KT AV4000 KT AV5000 SF4 5YO 80 Q SF4 4YO 80 Q P424220 01GA Y200 Y300 Y400 Y600 Y200T Y300T Y400T Y600T EAV2000 5000 0 0 1...

Page 3: ...Q EAV5000 F06 4YO Q EAVA5000 F10 EAV5000 F10 5YO Q EAV5000 F10 4YO Q EAVA EAV D F G H I J L N Q U P A R S EAV2000 G1 4 66 125 5 31 22 40 G1 8 38 0 67 5 84 5 10 5 29 23 5 4 36 8 40 EAVA2000 G1 8 24 76...

Page 4: ...109 SMC EAV2000 5000 2 3 1 R 7 1 2 5 2 3 1 4 R 6 R 1 2 1 2 _...

Page 5: ...G1 4 G3 8 G1 2 G3 4 G1 1 5 0 2 1 0 1 8 0 60 1 P 2 A 20 37 61 113 122 2 A 3 R 24 49 76 132 141 0 64 0 74 1 0 1 9 1 84 0 52 0 62 0 88 1 78 1 72 100 200 110 120 220 240 50 60 12 24 15 10 B 130 5 6 50 5...

Page 6: ...03 DZM 3 8 76 12 5 118 36 57 34 48 64 AVL4000 04 1 2 98 133 47 61 52 64 AVL4000 04 DZM 1 2 98 133 47 61 34 52 64 AVL5000 06 AVL5000 10 3 4 1 128 161 59 77 74 64 AVL5000 06 DZM AVL5000 10 DZM 3 4 1 128...

Page 7: ...pply exhaust function F R L combinations Modular with F R L combinations SMC AC2000 AC2500 AC3000 AC4000 AV2000 AV3000 AV4000 AC5000 AC6000 AV5000 F R L combination Soft start up valve Except AC4000 0...

Page 8: ...z 24VDC 12VDC Other Electrical entry G D Y Grommet Type D DIN terminal Type Y DIN terminal Indicator light Surge voltage suppressor Nil S Z None With surge voltage suppressor grommet type only With in...

Page 9: ...lever type AV4000 1 2 61 76 0 74 113 132 1 60 122 141 1 54 Secondary pressure MPa Needle valve flow characteristics Air flow l min ANR Conditions Primary pressure 0 5MPa Needle rotations Description...

Page 10: ...ntrolled by the usual meter out control When pilot valve is turned OFF spring pushes piston A and main valve upward and opens R port while shutting off the air supply from P port The pressure differen...

Page 11: ...24209A P424211 P424212 P424213 P424214 G 5 0 9 P424210 P424218 10 x 8 x 1 AV3000 P424304A P424305A P424306A P424307 P424308A P424309A P424311 P424312 P424313 P424314 STW 5 0 10 P424310 P424315 11 x 9...

Page 12: ...5 62 5 74 Dimensions Grommet AV 00 G GS SMC MADE IN JAPAN SMC MADE IN JAPAN ON OFF OFF ON 300mm lead wire length Manual override locking lever type Port size 36 8 E 37 N C Q H Pressure gauge mounting...

Page 13: ...Y30 Y40 Y60 AV2000 AV3000 AV4000 AV5000 Applicable model Model Spacer L type bracket Spacer with L type bracket Spacer with L type bracket L type bracket T type bracket Spacer with T type bracket Spac...

Page 14: ...should be performed by trained and experienced operators 3 Do not service machinery equipment or attempt to remove components until safety is confirmed 1 Inspection and maintenance of machinery equip...

Page 15: ...ulator AR2560 to 6060 With a standard regulator AR1000 to 6000 the secondary side pressure may not be released when this valve is exhausted 5 Operation of secondary side solenoid valves To operate sol...

Page 16: ...products When connecting piping to a product refer to its instruction manual to avoid mistakes regarding the supply port etc 5 F R L module combination When connecting to a modular F R L combination A...

Page 17: ...rated connected equipment will be actuated Confirm safety before operating Maintenance Warning 1 Drainage removal Remove drainage from air filters regularly Refer to specifica tions Caution 1 Do not u...

Reviews: