4 Settings 

4.1  Initial speed adjustment  

To  perform  the  initial  speed  adjustment  of  the  outlet  side  actuator, 
supply air from this valve’s inlet side and turn ON the pilot valve. Then, 
rotate the needle counterclockwise from the fully closed position. 

 

 

 

 

 

 

4.2  How to Find the Flow Rate 

(At air temperature of 20°C)

 

   Choke flow: (P2+0.1)/(P1+0.1) 

0.5 

                  

 

          

   

       

 

Subsonic flow, when:

   

  

 

         

 

            

 

                 

 

   

 

   

 

          

   

       

 

Q: Air flow rate [L/min (ANR)] 
S: Effective area [mm

2

P

1

: Inlet pressure [MPa] 

P

2

: Outlet pressure [MPa] 

t: Air temperature [

O

C] 

NOTE: 

The above formulas above are applied to pneumatics only  

4.3 Manual override 

Warning 

Since  connected  equipment  will  operate  when  the  manual  override  is 
activated, confirm that conditions are safe prior to activation. 

4.3.1 Push-turn locking slotted type [Type B] 

While pressing, turn in the direction of the arrow. 
If it is not turned, it can be operated in the same way as the non-locking 

type. 
 
 
 
 
 
 
 
 
 
 
 

Caution 

When  operating  the  locking  type  D  with  a  screw  driver,  turn  it  gently 
using a watchmakers screw driver [Torque: Less than 0.1N

m] 

 

4.3.2 Push-turn locking lever type [Type C] 

While pressing, turn in the direction of the arrow.  
If it is not turned, it can be operated in the same way as the non-locking 
type. 
 
 
 
 
 
 
 
 
 
  

 

Caution 

When locking the manual override on the push-turn locking type (B, C), 
make sure to push it down before turning.  Turning without first pushing  

4 Settings - continued 

it down can cause damage to the manual override and failures such as 
air leakage, etc.  
 

4.3.3 Non-Locking push type (AV-A-X2004) 

Press the blue button to override solenoid valve.   
 
 
 
 
 
 
 
 
 
 
 
 

5 How to Order 

Refer to catalogue 

and drawings for “How to Order” 

6 Outline Dimensions (mm) 

Refer to catalogue for outline dimensions. 

7 Maintenance 

  Not  following  proper  maintenance  procedures  could  cause  the 

product to malfunction and lead to equipment damage. 

  If handled improperly, compressed air can be dangerous. 

  Maintenance  of  pneumatic  systems  should  be  performed  only  by 

qualified personnel. 

  Before  performing  maintenance,  turn  off  the  power  supply  and  be 

sure to cut off the supply pressure. Confirm that the air is released to 
atmosphere. 

  After  installation  and  maintenance,  apply  operating  pressure  and 

power  to  the  equipment  and  perform  appropriate  functional  and 
leakage tests to make sure the equipment is installed correctly. 

  If  any  electrical  connections  are  disturbed  during  maintenance, 

ensure they are reconnected correctly  and safety checks are carried 
out  as  required  to  ensure  continued  compliance  with  applicable 

national regulations. 

  Do not make any modification to the product. 

  Do  not  disassemble  the  product,  unless  required  by  installation  or 

maintenance instructions. 

  Removal of equipment, and supply/exhaust of compressed air 

Before  equipment  removal,  ensure  that  measures  are  in  place  to 
prevent falling or run-away of the driven objects. Then, cut off the air 
supply,  electric  power  and  exhaust  air  pressure  from  the  system 
using the residual pressure release function. 

  If  handled  improperly,  damage  or  malfunction  of  machinery  or 

equipment may occur.  

  

Low frequency operation: 

Valves  should  be  operated  at  least  once  every  30  days  to  prevent 
malfunction (use caution regarding the air supply) 

Caution 

  

Drain flushing

 

Remove drained fluid from air filters periodically. 

8 Limitations of Use 

8.1 Limited warranty and Disclaimer/Compliance Requirements 

Refer to Handling Precautions for SMC Products. 

8.2 Safety relays 

Warning 

If a safe output from a safety relay or PLC is used to operate this valve, 
ensure that any output test pulse duration is shorter than 1 ms to avoid 
the valve solenoid responding. 

 

 

 

 

 

Limitations of Use - continued 

 

Warning 

Soft start function is not to be used as a safety function. 
 

8.3 failure modes 

The system designer should determine the effect of the possible failure 
states on the system 
 

Energy source status 

Single 

Air supply present, electricity 
cut 

Spool returns to the off position by 
spring force 

Air supply cut before electricity 
cut 

Spool returns to the off position by 
spring force 

Air supply cut after electricity 
cut 

Spool returns to the off position by 
spring force 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

9 Contacts 

Refer to Declaration of Conformity or  www.smcworld.com for contacts. 

 

URL : 

http// www.smcworld.com (Global)      http// www.smceu.com (Europe)

 

'SMC  Corporation,  Akihabara  UDX15F,  4-14-1,  Sotokanda,  Chiyoda-ku,  Tokyo 

101 0021 

Specifications are subject to change without prior notice from the manufacturer.  

© 

2018 

SMC Corporation All Rights Reserved. 

Template DKP50047-F-085H

 

Output signal 

Test pulse 

Reviews: