Wersja 1.00
Data edycji: 16.09.2022 r.
Strona 26 z 35
Dokumentacja techniczno-ruchowa
KWP-P-E
Arrangement 4
–
battery consisting of four fire dampers KWP (Figure 14)
The assembly of battery consisting of four fire dampers KWP is divided into two steps:
▪
Step 1
–
assembly of fire damper A and fire damper B and assembly of fire damper C and fire damper D.
▪
Step 2
–
assembly of the set of fire dampers A, B and the set of fire dampers C, D.
STEP 1:
a.
Fix the gasket on insulating spacer of one of adjoining fire dampers (position (1) in the Figure 14).
b.
Set together the sides of fire damper A and the fire damper B (where the gasket was fixed) and assemble them
together on the front and back with use of perforated assembly strips (2) and self-tapping screws M6x10 (3),
which should be tightened into the openings in fire damper body. In order to carry out the correct assembly, 4
self-tapping screws should be used per each assembly strip with length of 1200 [mm].
c.
Repeat paragraph 2 to assemble fire damper
C
on the fire damper
D
.
Figure 36. Battery made of four dampers KWP-O