Wersja 1.00
Data edycji: 16.09.2022 r.
Strona 20 z 35
Dokumentacja techniczno-ruchowa
KWP-P-E
Figure 8. Installation method of fire dampers KWP-O in ceiling with a fire ventilation duct with sealing of cement
mortar
Actuator under ceiling
Actuator above ceiling
E [mm]
Thickness of ceiling - 28
96
For ceiling with thickness greater than 150 [mm]: connect the damper to the duct before the damper isolation with
cement mortar (the damper frame will be bricked up along with a part of the duct).
Figure 9.Proposed dimensions of mounting brackets for installation in a ceiling