Technical parameters of iSWAY-
RFC® devices
Table 9.8. Technical parameters iSWAY-RFC.
Type
1.5
2.2
3.0
4.0
5.5
7.5
Airflow [m
3
/h]
10 000 12 000 20 000 25 000 36 000 40 000
Available
compression ratio
[Pa]
200
250
250
250
250
250
Total weight [kg]*
100
120
140
160
210
215
Operating
temperature [°C]
from -25 to +55
*according to Fig. 9.6
Table 9.9. Technical parameters - electric iSWAY-WFC
®
.
Type
Supply
voltage
Active
power
Apparent
power
[V]
[kW]
[kVA]
1.5
3x400
2.52
2.57
2.2
3x400
3.34
3.40
3.0
3x400
4.11
4.19
4.0
3x400
5.25
5.36
5.5
3x400
6.93
7.07
7.5
3x400
9.19
9.37
10.
Transport and storage
Do not store the aeration unit by placing one block on top of another.
The aeration unit should be stored indoors:
•
Relative humidity φ<80% at t=20°C
•
Ambient temperature -
40°C < t < +60°C
•
Aeration unit should not come into contact with dusts, gases and caustic fumes and other
chemicals that could corrode equipment and components aeration units.
For the storage period, the foil packaging must be unsealed.
❖
Any damage resulting from improper transportation, unloading and storage is not covered
by the warranty and claims on this account will not be respected by SMAY Sp. z o.o.
In addition, the device is supplied with:
•
Wiring pipes - 12 m
•
Fittings for wiring pipes - 3 pcs.
•
Clamps for wiring pipes - 12 pcs.
•
PVC hose ø 5mm