Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
32
RAL9006 mat
AL - frame and lamella profiles made of powder coated aluminum
<RAL> - according to RAL palette (for AL finish)
* default values - default values will be used if optional values are not specified
Order example:
iSWAY
–
WFC
–
3.0 - AA
8.2.3.
iSWAY-RFC
®
labelling
iSWAY- RFC-<W>-<U>-<Y>-<Dc>-<P><RAL>/<ADD>
<W> - the size/type of the device housing:
1.5
–
10000 [m
3
/h] unit capacity with available compression ratio of 200 Pa
2.2
–
12000 [m
3
/h] unit capacity with available compression ratio of 250 Pa
3.0
–
20000 [m
3
/h] unit capacity with available compression ratio of 250 Pa
4.0
–
25000 [m
3
/h] unit capacity with available compression ratio of 240 Pa
5.5
–
36000 [m
3
/h] unit capacity with available compression ratio of 250 Pa
7.5
–
40000 [m
3
/h] unit capacity with available compression ratio of 270 Pa
<U> - location of SzA-FCK automation cabinet *
none = inside the building
Z
–
outside the building
<Y> - additional 24VDC outputs*
none = no additional 24VDC outputs
M - has an output for KSN vent, 24VDC power output for TSS, 24VDC output for peripheral device
<Dc>- additional pressure sensor*
none = no additional pressure sensor
PF
–
PMAC-F standard pressure sensor (as a standard, there is one pressure sensor in the
MAC-FC in the SzA-FCK automation cabinet)
<P> - finishing (relates also for accessories: TR1, TR3, TR6, UP, SRC-D, KCD)
SO - galvanized steel
SL
–
powder coated steel
<RAL> - according to RAL palette (for SL finish)
<ADD>- accessories:
TR1 - AxB size connector (only for vertical installation)
TR3 - AxB size connector (only for vertical installation)
TR6 - AxB size connector (only for vertical installation)
UP - double air intake dumpers AxB size
SRC-D - AxB size damper with enclosed smoke detector (for horizontal installation
recommended with ZS)
KCD - smoke detector duct
with AxB size and length L=400mm (only for horizontal
installation), note: select always with CDH-K air intake
CDH-K-A-<P><RAL>-BF24
–
CDH-K damper of CxD dimension (only for horizontal
installation)
<P> - finish