Drive Startup Manual KEB-Induction
Page 12
© 2020 Smartrise Engineering, Inc. All Rights Reserved
March 5, 2020
Appendix 3 Advanced Troubleshooting
The following list of troubleshooting steps are to help with the startup and smooth operation of
the drive.
Starting Over (Defaulting Drive)
Sometimes parameters get changed, or certain functions that should work are not working for
no apparent reason. In this case, starting over with factory defaults may solve these issues.
Perform the following to default the drive to factory settings.
Navigate to US03 and load the opposite configuration of what is shown.
To load opposite configuration:
a.
If the original configuration is Gearless, navigate to PM | Induction |Gearless and
load (Induction) Geared and Save. Go to step 3.
b.
If the original configuration is Geared, navigate to PM | Induction |Geared and load
(Induction) Gearless and Save. Go to step 4.
After this value is saved, go back and load the original configuration as Gearless. This
does a complete background default on the drive. Go to step 5.
After this value is saved, go back and load the original configuration as Geared. This
does a complete background default on the drive.
Navigate to US05 and select Write Configuration to Drive.
Perform the following to re-load OEM values (Programmed by Smartrise).
Go to US05 and select Restore OEM Defaults to reload Smartrise settings.
Vibration
If any vibration occurs:
Cut the KP (LC03, LC04) and KI (LC08, LC09) gains in half.
Motor Noise
If the motor sounds noisy:
Change LE.05 to 8 (PM)
Motor Not Running When Given Command
Perform the following when a motor is not running with given command.
Check LI.01: Needs to be NPN for the drive to receive signals from controller.
Verify parameters LF.41 through LF.43 are set to the correct value. See Parameter table
on the prints.
Summary of Contents for KEB-Induction
Page 1: ......