load has exceeded the set value or the HC request value has exceeded the set value;
c)
After the genset has started up, synchronization, parallel and share load process will begin;
d)
The genset will stop according to the preset sequence if the load has fallen below the set value
(light load input deactivates.)
14.
INSTALLATION
Controller is split type design; HPM6D display module is panel mounted and it is fixed by 4 clips
when installed while HPM6M master control module is fixed by M5×4 screw. The controller’s overall
dimensions and cutout dimensions are as following:
Fig.26 – HPM6D Display Module Installation Dimensions (Unit: mm)
Fig.27 – HPM6M Master Control Module Installation Dimensions (Unit: mm)
1)
Battery Voltage Input
NOTE:
HPM6 controller can suit for widely range of battery voltage (8~35) VDC. The wire’s diameter must be over
1.5mm
2
and which is connected to B+ and B- of controller power.
2)
Output and Expand Relays