![Smartgen HGMS62 User Manual Download Page 6](http://html1.mh-extra.com/html/smartgen/hgms62/hgms62_user-manual_1297538006.webp)
HGMS62 Split Type Genset Controller User Manual Page 6 of 58
1
OVERVIEW
HGMS62 Genset Controller
adopts
split structure of “Master Control and Display”, integrating
digital, intelligent and network techniques, is used for automatic control and monitoring system of
genset. It can carry out functions of automatic start/stop, data measurement, alarm protection and
“four remote” (remote control, remote measure, remote communication and remote adjustment). The
controller uses monochrome LCD display, optional interface with multiple languages, which is easy and
reliable to operate.
HGMS62 Genset
Controller
uses 32-bit microprocessor technique which can achieve precision
measurement, value adjustment, timing and threshold setting etc. All the parameters can be configured
from front panel or use USB interface (or RS485 interface) to adjust via PC. It is equipped with fuse,
fuel, start relay and auxiliary output 3, 4 are pluggable. The compact structure and simple wiring of the
controller solve the problem of complex wiring and low efficiency, and improve the production
efficiency of the control cabinet. It can be widely used in various types of automatic control system.
2
PERFORMANCE AND CHARACTERISTICS
Display Module: HGMS62D, Master Control Module: HGMS62M, HGMS62MCAN.
HGMS62:
HGMS62M; HGMS62CAN: HGMS62MCAN.
HGMS62D:
Display control module.
HGMS62M:
MPU interface, suitable for ESC controlled engines.
HGMS62MCAN:
CAN BUS interface, suitable for ECU controlled J1939 engines.
Different harnesses are available:
XS-HGMS62DM
(standard backpack screen installation method),
XS-HGMS62DM-S
(sound-attenuating cabinet installation method), details see 7.3 HGMS62 harness description.
Other lengths need to be customized.
NOTE:
HGMS62 is taken as an example for following descriptions.
HGMS62:
mains/gen power monitoring, used for mains/gen automatic transfer (AMF), suitable for
single unit automation system with one mains and one generator. It can disable mains by setting
parameters for single unit automation, control genset auto start/stop vis remote start signal.
Its main features are as follows:
—
132x64 resolution LCD with backlight, optional language interface (Chinese, English, others),
can be selected through the panel on site, which is convenient for debugging personnel;
—
With RS485 communication port, can achieve “four remote” functions (remote control, remote
measurement, remote communication and remote adjustment) via MODBUS protocol;
—
Adapt to 3P4W, 3P3W, 1P2W and 2P3W (120V/240V), 50Hz/60Hz power system;
—
Can measure and display 3-phase voltage, 3-phase current, frequency, power parameter of
mains/gen;
Mains
Gen
Line voltage Uab, Ubc, Uca Line voltage Uab, Ubc, Uca
Phase voltage Ua, Ub, Uc Phase voltage Ua, Ub, Uc
Frequency Hz Frequency Hz
Phase sequence Phase sequence
Load
Current Ia, Ib, Ic A