HGMS62 Split Type Genset Controller User Manual Page 46 of 58
c)
Press
in this interface can display boot screen.
9.6
DATE AND TIME
This item can calibrate controller date and time.
9.7
BATTERY UNDER VOLTAGE START
This item can set battery under voltage start enable, start value, stop value, delay value.
10
SENSOR SETTING
—
When re-choosing sensor, standard value of sensor curve will be needed. If default temperature
sensor is set as SGH (120ºC resistance type), sensor curve should be SGH (120
o
C resistance type);
If it is set as SGD (120ºC resistance type), sensor curve should be SGD curve.
—
If there is difference between standard sensor curve and chosen sensor curve, select “Defined
Sensor”, and then input defined sensor curve.
—
When sensor curve is inputted, X value (resistance) must be in accordance with the order of lower
to higher, otherwise errors will occur.
—
When sensor is selected as “None”, sensor curve is inactive.
—
If there is only alarm switch for corresponding sensor, this sensor must be set as “None”,
otherwise alarm shutdown or warning may appear.
—
Can set several points of forehand or backmost as the same ordinate, as the following picture:
Fig.4 – Sensor Curve Diagram
Table 18 – Normal Pressure Unit Conversion
Item
1N/m
2
(pa)
1kgf/cm
2
1bar
(1b/in
2
) psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1