HGMS62 Split Type Genset Controller User Manual Page 18 of 58
No.
Shutdown
Description
18 Level Sensor Open
When level sensor is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
19 Low Level
When level value is lower than threshold, controller will send shutdown
alarm signal.
20 Aux. Sensor 1 Open
When aux. sensor 1 is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
21 Aux. Sensor 1 High
When aux. sensor 1 value is higher than threshold, controller will send
shutdown alarm signal.
22 Aux. Sensor 1 Low
When aux. sensor 1 value is lower than threshold, controller will send
shutdown alarm signal.
23 Aux. Sensor 2 Open
When aux. sensor 2 is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
24 Aux. Sensor 2 High
When aux. sensor 2 value is higher than threshold, controller will send
shutdown alarm signal.
25 Aux. Sensor 2 Low
When aux. sensor 2 value is lower than threshold, controller will send
shutdown alarm signal.
26 Input Shutdown
When digital input is active for shutdown alarm, controller will send
shutdown alarm signal.
6.3
TRIP AND STOP ALARMS
When controller detects trip and stop alarm signal, it will disconnect gen close signal immediately
and stop after cooling.
Table 8 – Trip and Stop Alarms
No.
Trip and Stop
Description
1 Over Current
When genset current is higher than threshold and overcurrent action
selects “Trip and Stop”, controller will send trip and stop alarm signal.
2 Maintenance Due
When maintenance countdown is 0 and maintenance date is due,
maintenance due action selects “Trip and Stop”, controller will send trip
and stop alarm signal.
3 Reverse Power
When genset reverse power value (power is negative) is higher than
threshold, and reverse power action selects “Trip and Stop”, controller
will send trip and stop alarm signal.
4 Over Power
When genset power value (power is positive) is higher than threshold,
and over power action selects “Trip and Stop”, controller will send trip
and stop alarm signal.
5 Input Trip and Stop
When input port is configured as “Trip and Stop” and active, controller
will send trip and stop alarm signal.