HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 46 of 58
7.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL
ACTIVE WHEN CONNECT TO GRAND (B-))
Form 3
No.
Type
Description
0
Users Configured
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and
shutdown after hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run
delay.
1
Reserved
2
Alarm Mute
Can prohibit
“Audible Alarm” output when input is
active.
3
Reset Alarm
Can reset shutdown alarm and trip alarm when
input is active.
4
Reserved
5
Lamp Test
All LED indicators are illuminating when input is
active.
6
Panel Lock
All
buttons
in
panel
is
inactive
except
and there is
in the left of
first row in LCD when input is active.
7
Reserved
8
Idle Control Mode
Under voltage/frequency/speed protection is
inactive.
9
Inhibit Auto Stop
In
Auto
mode, during generator normal running,
when input is active, inhibit generator shutdown
automatically.
10
Inhibit Auto Start
In
Auto
mode, inhibit generator start automatically
when input is active.
11
Inhibit Scheduled
In
Auto
mode, inhibit scheduled run genset when
input is active.
12
Reserved
13
Aux Gen Closed
Connect generator
loading switch‟s Aux. Point.
14
Inhibit Gen Load
Prohibit genset switch on when input is active.
15
Aux Mains Closed
Connect mains loading switch‟s Aux. Point.
16
Inhibit Mains Load
Prohibit mains switch on when input is active.
17
Auto Mode Lock
When input is active, controller enters into Auto