HGM8151 Genset Parallel Controller User Manual Page 11 of 66
Icons
Keys
Description
Right
1) Screen scroll;
2) Right move cursor in setting menu.
Confirm
Confirm input content in setting menu.
Exit
1) Return to main menu;
2) Return to previous menu in setting menu.
NOTE:
Press
and
simultaneously in manual mode will force generator to crank. Successful start
will not be judged according to crank disconnect conditions, operator will have to crank the starter motor manually; when
operator decides that the engine has fired, he/she should release the button and start output will be deactivated, safety
on delay will be initiated.
WARNING!
Default password is 00318, user can change it in case of others change the advanced parameters setting.
Please clearly remember the password after changing. If you forget it, please contact SmartGen services and send all
information
in the controller page of “
ABOUT
” to us
.
4.3
LCD DISPLAY
4.3.1
MAIN DISPLAY
Main screen show pages; use
to scroll the pages and
to scroll the screen.
⚫
Main Screen
, including as below,
Part of status display
Gen: voltage, frequency
Load: current, active power, reactive power
Bus: voltage, frequency
Engine: speed, temperature, oil pressure
NOTE:
Main screen will circulatory display if without scroll operation.
⚫
Status
, including as below,
Status of genset and ATS
⚫
Engine
, including as below,
Engine speed, engine temperature, engine oil pressure, fuel level, flexible sensor 1, flexible sensor 2,
battery voltage, charger voltage, engine accumulated run, accumulated start times and user A and B
accumulated running time.
NOTE:
If connected with J1939 engine via CANBUS port, this page also includes: coolant pressure, coolant level, fuel
temperature, fuel pressure, inlet temperature, exhaust temperature, turbo pressure, total fuel consumption and so on.
(Different engine with different parameters).
⚫
Generator,
including as below,
Phase voltage, line voltage, frequency, phase sequence, each phase current, each phase and total
active power (positive and negative), each phase and total reactive power (positive and negative), each