HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
10
of
68
3 SPECIFICATION
Parameter
Details
Working Voltage
DC8. 0V to 35. 0V, continuous power supply
Overall Consumption
<3W (Standby mode: ≤2W)
Speed Sensor Voltage
1. 0 V to 24 V (RMS)
Speed Sensor Frequency
Maximum 10,000 Hz
Start Relay Output
16A DC28V power supply output
Fuel Relay Output
16A DC28V power supply output
Configurable Relay Output 1
7A DC28V power supply output
Configurable Relay Output 2
7A AC250V passive output
Configurable Relay Output 3
16A AC250V passive output
Configurable Relay Output 4
16A AC250V passive output
Configurable Relay Output 5
7A DC28V power supply output
Configurable Relay Output 6
7A DC28V power supply output
Case Dimensions
197mm x 152mm x 47mm
Panel Cutout
186mm x 141mm
Working Conditions
Temperature: (-25~+70)°C
Humidity: (20~93)%RH
Storage Conditions
Temperature:(-25~+70)°C
Protection Level
IP55 Gasket
Insulation Intensity
Apply AC2.2kV voltage between high voltage terminal
and low voltage terminal;
The leakage current is not more than 3mA within 1min.
Weight
0.75kg