HEM8500 Engine CAN Monitoring Controller User Manual Page 16 of 45
Table 10 Parameter Setting Example (Screen 4)
>Return
>Pre-heat Delay
>Cranking Time
>Crank Rest Time
>Safety On Delay
>Cooling Time
>ETS Solenoid Hold
>Fail to Stop Delay
>Power Off Delay
Screen 4:
Use
to change settings and
to move setting
numbers and confirm setting data.
00010s
NOTE:
press
and it can exist parameter settings directly.
5.3
START/STOP OPERATION
a)
Press start key, then engine is cranking;
b)
“Preheat Delay XX s” information will be displayed on LCD;
c)
After the preheat delay, Starter relay is engaged. If the engine fails to fire during this cranking
attempt then the Starter relay stop outputting; “Crank Rest Time” begins and wait for the next crank
attempt;
d)
During the set start attempts, if engine fails to start, it will issue failed to start alarm;
e)
In case of successful crank attempt, the “Safety On” timer is activated. As soon as this delay is
over, engine enters into normal running status;
f)
During the engine normal running process, when manual throttle is active, users can adjust engine
speed through manual throttle knob;
g)
Press stop key, engine enters into stopping process;
h)
Engine enters “ETS Solenoid Hold”. ECU power off and ETS delay timer is energized;
i)
After ETS delay is over, it enters into “After Stop” delay;
j)
Engine is placed into its standby mode after its “Waiting for Stop” delay expired.