HAT833 Series Three Power ATS Controller User Manual Page 25 of 56
9
PARAMETERS CONFIGURATION
9.1
ILLUSTRATION
In the main interface, press
key, choose
Configuration
and press
again to enter
into password confirmation interface. If password is correct, enter into parameter setting interface,
otherwise, exit to main interface directly. Factory default password is
01234
. In parameters
configuration interface, pressing
key to return the prior menu.
9.2
PARAMETERS TABLE
Table 18 – Parameter Configuration Form
No.
Item
Range
Default
Description
AC Config
1
S1 Volt Normal
(0~3600)s
10
The delay from S1 voltage abnormal to
normal.
2
S1 Volt Abnormal
(0~3600)s
5
The delay from S1 voltage normal to
abnormal.
3
S2 Volt Normal
(0~3600)s
10
The delay from S2 voltage abnormal to
normal.
4
S2 Volt Abnormal
(0~3600)s
5
The delay from S2 voltage normal to
abnormal.
5
S3 Volt Normal
(0~3600)s
10
The delay from S3 voltage abnormal to
normal.
6
S3 Volt Abnormal
(0~3600)s
5
The delay from S3 voltage normal to
abnormal.
7
Master Set
(0~5)
0
0: S1>S2>S3
1: S2>S1>S3
2: S3>S1>S2
3: S1>S3>S2
4: S2>S3>S1
5: S3>S2>S1
8
System Type
(0~7)
6
0: S1M S2G S3M
1: S1G S2M S3M
2: S1M S2M S3M
3: S1G S2G S3M
4: S1M S2G S3G
5: S1G S2M S3G
6: S1M S2M S3G
7: S1G S2G S3G
9
AC System
(0~3)
0
0: 3 Phase,4 Wire (3P4W)
1: 3 Phase,3 Wire (3P3W)
2: 2 Phase,3 Wire (2P3W)
3: Single Phase,2 Wire (1P2W)