HAT700 SERIES ATS CONTROLLER USER MANUAL
HAT700 Series ATS Controller 2018-12-13 Version 1.5 Page 17 of 51
8 START/STOP OPERATION
8.1 MANUAL START/STOP
8.1.1. PANEL START/STOP
In the main screen, press
key will enter into manual start operation interface.
1.Return
2.Stop Genset
3.Start Genset
Press
Up/Down
key to choose parameters (the current line was
highlighted with black) and then press
Confirm
key to confirm.
Genset Stop
:
Disconnect the start signal, i.e. stop the running genset.
Genset Start
:
Output the start signal, i.e. start the genset.
When system is “S1 Gen S2 Gen”, manual start/stop menu interface is as follows:
1.Return
2.S1 Genset Stop
3.S1 Genset Start
4.S2 Genset Stop
5.S2 Genset Start
Press
Up/Down
key to choose parameters (the current line was
highlighted with black) and then press
Confirm
key to confirm.
S1 Genset Stop
:
Disconnect the S1 start signal, i.e. stop the running S1 genset.
S1 Genset Start
:
Output the S1 start signal, i.e. start the S1 genset.
S2 Genset Stop
:
Disconnect the S2 start signal, i.e. stop the running S2 genset.
S2 Genset Start
:
Output the S2 start signal, i.e. start the S2 genset.
8.1.2. REMOTE START/STOP
Send remote start/stop signals using MODBUS protocol via RS485 port.
Remote Stop
:
Disconnect the start signal, i.e. stop the running genset.
Remote Start
:
Output the start signal, i.e. start the genset.
8.2 AUTO START/STOP
8.2.1 INPUT PORT START/STOP OPERATION
Set input
port as “Remote Start On Load” or “Remote Start Off Load”, both could not be set
simultaneously.
Remote Start on Load
:
When the input is active, genset close relay will active after genset is normal;
when the input inactive, genset will stop automatically.
Remote Start off Load
:
When the input is active, mains close relay will active after mains is normal;
genset close relay will active when the mains is abnormal while genset is normal; when the input inactive,
genset will stop automatically.