HAT700 SERIES ATS CONTROLLER USER MANUAL
HAT700 Series ATS Controller 2018-12-13 Version 1.5 Page 11 of 51
7 LCD DISPLAY
7.1 MAIN SCREEN
Status
S1 Normal
S2 Inactive
Genset Standby
S1 On Load
Auto Mode
S1 Voltage Status
S2 Voltage Status
Genset Status
Switch Status
Current Mode, Alarm Status, Indications, Others
Power
U1LL 380 380 380V
U1LN 220 220 220V
Phase 0 120 240°
F1 50.00Hz BAT 27.5V
Auto Mode
S1 Line Voltage (L1-L2
、
L2-L3
、
L3-L1)
S1 Phase Voltage
S1 Phase
S1 Frequency and genset battery voltage
Current Mode, Alarm Status, Indications, Others
U2LL 0 0 0V
U2LN 0 0 0V
Phase #### #### ####°
F2 0.00Hz Load 100%
Auto Mode
S2 Line Voltage(L1-L2
、
L2-L3
、
L3-L1)
S2 Phase Voltage
S2 Phase
S2 Frequency and present on-load percentage.
Current Mode, Alarm Status, Indications, Others
Load
I 500 500 500A
Phase 0 120 240°
TkW 329 PF 1.00
Tkvar 1.3 TkVa 330
Auto Mode
3-phase current
3-phase current phase
Total active power, power factor
Total reactive power, Total apparent Power.
Current Mode, Alarm Status, Indications, Others
kW 126 129 130
kvar 0.5 0.8 0.7
kVA 127 129 131
PF 1.00 1.00 1.00
Auto Mode
3-phase active power
3-phase reactive power
3-phase apparent power
3-phase power factor
Current Mode, Alarm Status, Indications, Others
Sync
Volt Diff. 74V x
Freq Diff. 0.13Hz ok
Phase Diff. 12° x
Auto Mode
Volt Diff., D-value of 3-phase volt mean
Freq Diff.
Phase Diff.
Current Mode, Alarm Status, Indications, Others
Total
Cont. Power Suppy Time
5:25:18
Last Cont. Powe Supply
8:15:37
Auto Mode
Cont. Power Suppy Time
HH
:
MM
:
SS
Last Cont. Powe Supply
HH
:
MM
:
SS
Current Mode, Alarm Status, Indications, Others
S1 Total Supply Time
125:25:18
S1 Total Supply Time
HH
:
MM
:
SS