background image

                                                             

HAT600N Series ATS Controller User Manual 

HAT600N  Series  ATS  Controller                      Version  1.1                  2019-09-05                Page  5  of  24

 

Table 2 HAT600N Series Controller Models and Main Functions 

Type

 

DC Power Supply 

AC Power Supply 

AC Current and Power 

HAT600N 

√ 

× 

× 

HAT600NI 

√ 

× 

√ 

HAT600NB 

√ 

√ (LN220V) 

× 

HAT600NBI 

√ 

√ (LN220V) 

√ 

3.  SPECIFICATION 

Table 3 Technical Parameters 

Items 

Contents 

Operating Voltage 

DC 8.0V~35.0V, continuous power supply. 
HTS220/HWS560 power supply (without battery supply). 
AC160V~280V (HAT600NB/HAT600NBI) during AC power L1N1/L2N2 supply. 

Power Consumption 

<3W (Standby mode: ≤2W) 

AC Voltage Input 

AC system 

HAT600N/HAT600NI 

HAT600NB/HAT600NBI 

3P4W (L-L) 

(80~625)V 

(80~480)V 

3P3W (L-L) 

(80~625)V 

Not used 

1P2W (L-N) 

(50~360)V 

(50~280)V 

2P3W (A-B) 

(80~625)V 

(80~480)V 

Rated Frequency 

50/60Hz 

Close / Open Trip 
Relay Output 

16A    AC250V 

 

Free Voltage relay output 

Programmable 
Relay Output   

16A/7A    AC250V    Free Voltage relay output 

Digital Input 

Connecting to GND 

Communication 

RS485 isolated interface, ModBus Protocol 

Dimensions 

209mmx153mmx55mm 

Panel Cutout 

186mm x 141mm 

Operating Temp. 
Range 

Temperature: (-25~+70)°C;      Humidity: (20~93)%RH 

Storage Condition 

Temperature: (-25~+70)°C 

Protection Rank 

IP55: when waterproof gasket is installed between enclosure and control screen.   

Insulation Strength 

Apply AC2.2kV voltage between high voltage terminal and low voltage terminal 
and the leakage current is not more than 3mA within 1min. 

Weight 

0.8kg(HAT600N,HAT600NI)/1.0kg(HAT600NB/HAT600NBI) 

 

Summary of Contents for HAT600N Series

Page 1: ...HAT600N SERIES HAT600N HAT600NI HAT600NB HAT600NBI ATS CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...ing or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of thi...

Page 3: ...TION 5 4 OPERATING 6 5 LCD DISPLAY 7 6 COMMISSIONING 9 7 PARAMETERS CONFIGURATION 10 8 EVENT LOG 14 9 TIMING START 15 10 DATE AND TIME SETTING 15 11 LANGUAGE SETTING 15 12 CONTROLLER INFORMATION 16 13...

Page 4: ...cy F2 4 Measure and display load active power apparent power power factor and 3 phase current 5 Over current alarm function 6 Over under voltage loss of phase reverse phase sequence over under frequen...

Page 5: ...3P4W L L 80 625 V 80 480 V 3P3W L L 80 625 V Not used 1P2W L N 50 360 V 50 280 V 2P3W A B 80 625 V 80 480 V Rated Frequency 50 60Hz Close Open Trip Relay Output 16A AC250V Free Voltage relay output Pr...

Page 6: ...off 1 or 2 power to off load 2 Close In Manual mode switch on 2 power to load Manual Press and controller enters into Manual mode Automatic Press and controller enters into AUTO mode Test Pressing thi...

Page 7: ...Type Description 1 1 Gens Alarm Alarm When 1 genset occur failure this will display 2 1 Fail to Close Alarm When 1 breaker occur closing failure this will display 3 1 Fail to Open Alarm When 1 breake...

Page 8: ...hase sequence is not A B C 10 2 Volt Normal Indication 2 source voltage is within the setting range Table 7 Display Status of Other Items upper to lower No Item Type Description 1 Trip alarm Alarm Tri...

Page 9: ...s normal or not STOP TO TEST The start generator signal will turn off after pressing this key immediately CYCLE START When this mode is active generator start signal will cyclic output according to ma...

Page 10: ...l to voltage abnormal 03 2 Normal Delay 0 9999 s 10 It is the delay of 2 power from voltage abnormal to voltage normal 04 2 Abnormal Delay 0 9999 s 5 It is the delay of 2 power from voltage normal to...

Page 11: ...23 Under Frequency Return 0 0 75 0 Hz 48 0 Normal return value of over frequency 24 CT Ratio 5 65000 5 500 Current Transformer ratio 25 Rated Load Current 5 6000 A 500 Load rated current 26 Over Curre...

Page 12: ...7 3 INPUT OUTPUT FUNCTION DESCRIPTION Table 9 Input Port Function Description Item Description 01 Not used Invalid 02 Breaking compulsorily When active this will force the breaker to transfer the ATS...

Page 13: ...09 2 Abnormal volt It will output when 2 voltages is abnormal 10 Over current output It will output when loaded current exceeds the limit 11 Auto state output In will show output in automatic mode 12...

Page 14: ...it can display the record information circularly including the temporal voltage of 1 and 2 detailed voltage current frequency and date and time Press and it will exit the current interface while pres...

Page 15: ...ime Generator continuously run time can be set on the duration of maximum time for 99 hours 59 minutes 10 DATE AND TIME SETTING In the main screen press key and select 4 Date Time set and then press k...

Page 16: ...0 2009 10 11 12 CONTROLLER INFORMATION In the main screen press key and select 6 Controller information and then press key the screen will show the controller information interface as follow Display c...

Page 17: ...UPPLY The power of ATS is smartly controlled by controller As long as one power is normal it can ensures ATS voltage power supply normally and can be transferred properly Users should select power sup...

Page 18: ...can also be applicable to dual power switching management for factories telecom industrial and civil buildings achieving remote control remote measuring remote communication functions More information...

Page 19: ...gative DC negative input 20 B To start engine connect the terminal to battery positive DC positive input 8 35 V controller power supply 21 1 close input Detection of 1 switch closing state voltage fre...

Page 20: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 20 of 24 16 TYPICAL WIRING DIAGRAM Fig 3 ATYS3 Wiring Diagram Fig 4 SGQ N T Wiring Diagram...

Page 21: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 21 of 24 Fig 5 SGQ M Wiring Diagram Fig 6 VITZRO Wiring Diagram...

Page 22: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 22 of 24 Fig 7 Contactor Wiring Diagram Fig 8 ATYSM3S Wiring Diagram...

Page 23: ...9 09 05 Page 23 of 24 Fig 9 Breaker Wiring Diagram Remark all above are application diagrams of HAT600N series ATS controllers However HAT600N and HAT600NB have no current sample input please skip ove...

Page 24: ...ntroller with RS485 converter GND or PC GND It is recommended that a 120 resistor is added between A and B of RS485 Programmable output error Check programmable output connections and pay attention to...

Reviews: