HAT160 ATS CONTROLLER USER MANUAL
HAT160 ATS Controller 2020-03-14 Version 1.1 Page 5 of 21
2. PERFORMANCE AND CHARACTERISTICS
HAT160
controller can detect 2-way (2-way mains and 2-way gens or 1-way mains and 1-way gens)
3-phase/single phase voltages and control ATS.
Main characteristics are as below:
—
Measure and display 2-way 3 phase/single phase Voltage and Frequency:
1# 2#
Line voltage (Uab, Ubc, Uca) Line voltage (Uab, Ubc, Uca)
Phase voltage (Ua, Ub, Uc) Phase voltage (Ua, Ub, Uc)
Frequency Hz Frequency Hz
—
Over/under voltage, over/under frequency and loss of phase detection function, active or deactive
can be configured;
—
Close/Open failure alarm indication;
—
Panel LEDs can clearly display switch working status;
—
Auto/Manual mode transfer. In manual mode, ATS can be switched manually by pressing front
panel button;
—
2-way isolated N wire design.
—
ATS supply priority (1# Priority/2# Priority (Auto throw auto restore), No priority (auto throw non
restore), and 1#/2# power voltage normal/abnormal delay parameters can be set from front panel;
—
Re-closing function for power off;
—
Over close delay function and delay time is 0.5s;
—
If A phase voltage of any one way is normal, controller can control ATS to act. Under the
circumstance of A phase voltage of any one way is normal, if 2 way power voltages are abnormal at
the same time, ATS will automatically transfer to breaking (neutral) position;
—
Forced open input port (fire reset) is fitted; when input is active, ATS will automatically transfer to
breaking (neutral) position;
—
Parameter setting function: part of parameters can be adjusted from controller front panel, all
parameters can be adjusted via LINK port (use SG72A adaptor) on computer software;
—
Digital adjustment is applied for parameters, getting rid of analogue modulation method of
potentiometer, improving whole reliability and stability;
—
Extremely strong anti-electromagnetic interference ability, suitable for usage under complex
environment of strong electromagnetic interference;
—
Modular structure design, flame retardant ABS shell, pluggable wiring terminal, and compact
structure;
—
3 installation methods are offered: panel built-in, internal 35mm slideway and internal screw
mounting.