Dual Smoke / Heat Detector and
Combined Sounder
Installation Guide
Part number Product description
SC-22-0200-0001-99
Dual Smoke / Heat Detector and
Combined Sounder
1 Pre installation
2 Components
Mounting plate
3
Dust cover
1
2 Dual smoke / heat detector and combined sounder
!
Installation must conform to applicable local installation codes and
should only be installed by a fully trained competent person.
This device contains electronics that may be susceptible to damage
from Electrostatic Discharge (ESD). Take appropriate precautions
when handling electronic boards.
The use of a non-metallic spacer should be considered if mounting
the device on to a metal surface.
Batteries
(not included in some regions*)
4
5 Fit batteries
When fitting / replacing batteries, observe correct polarity, using only
specified batteries.
6 Configuration
ER14500
AA
ER14500
AA
+
-
+
-
ER14500
AA
+
-
The device must now be added (programmed) to the control panel.
Device powering
Method 1
Magnet application
Method 2
Via computer
Method 3
4 Fix mounting plate
When fixing to the ceiling, all four fixing positions should be used to
ensure a firm fixing.
Use suitable fasteners and
fixings.
60 mm
60 mm
Where existing electrical
mounting boxes are present,
two fixing positions may be
used.
3 Remove mounting plate
Remove the mounting plate by turning the device ANTICLOCKWISE, to
release it from the mounting plate.
OBSERVE BATTERY
POLARITY!
!
3x ER14505M
LITHIUM 3.6V
©2021 EMS Ltd. All rights reserved. Page 1 of 2
TSD090-0001-99 (Issue 3) 25/08/2021 AJM
3
1
2
4
*When batteries are not supplied, only fit specified batteries.
To ensure correct operation, products must be used within the
specified environmental operating conditions.
Refer to the programming manual
for full programming details.
SmartCell panel = TSD155
SmartCell WZM = MK067