Smallart THR-FCU-2025 User Manual Download Page 1

 

 

 

THR-FCU-2025 

ROOM CONTROL PANEL 

Doc: 00-15-01, V1.3, 20161113 

                                                                  Page 1 / 4 

Copyright © Smallart

®

 

www.smallart.com.tr 

THR-FCU-2025 User Manual 

THR-FCU-2025  is  designed  to  control  the  room  temperature  in  industrial, 

commercial  and  residential  environment  with  stand-alone microprocessor  and  large 

LCD display.  

It shows the following Items: working status (Cooling 

, Heating 

, Ventilation 

, Auto 

), valve output status (

), room temperature, set temperature, time and 

etc. With key: On/Off (

), Menu

( )

, Fan speed

,

 

Okey

, Adjustment 

▲▼

.

 

 

Basic Features                             

 

States Display 

 Manual/Auto control valves output 

 Manual 3-step fan speed changeover 

       

 Low temperature protection 

 Clock 

 Detect and display room temp. 

 

Working mode 

 

Fan speed 

 Display sensor detect temperature  

 

Display setting temperature 

 

Clock display

 

 

Display valve output

 

Specifications 

 Temperature sensor: NTC 

 

Control Accuracy: ±1

 

 Operation environment:0

45

 

 Humidity: 5

95% RH

non-condensing

 

 Button: push button 

 Power Consumption: 

 2 W 

 Protection Class: IP 30 

          

 Power supply: AC 24V, 50/60Hz or DC 24V 

 Wiring: Accepting

Accepting 2

×

1.5 mm

2  

Or 1

×

2.5 mm

2

 wires 

 Switch current rating: Resistive: 2 A, Inductive: 1 A 

 

 Housing: PC + ABS Flame Retardant 

 Frame size: 112

×

85

×

28.5 mm

L

×

H

×

W

 

 Hole pitch: 60 mm /83.5mm (Standard) 

Operation 

 ON/OFF: Press

for on/off and ECO mode 

 Temperature setting: press 

and 

▲”

to adjust temperature by 0.5

℃.

 

 Mode selecting: press 

“ ”

to select cooling 

“ ”, heating “ ”, ventilation “ ”or auto “

”; Auto mode 

is available only under 4-pipe system. 

Fan speed: press 

“ ” to set 

Low

Med

High

Auto

The  fan  speed  change  automatically  under  Auto  mode.  Auto  LOW  when  the  difference  between  room-

temperature and set-point exceed 1

; Auto MED when exceed 2

; Auto HIGH when exceed 3

.

 

 Clock setting: 

Press “

” into clock program function by hour, minutes and week, Press “

”and “

” to adjust. 

  ECO  mode:  press 

“ ”  to  enter  into  ECO  mode,  thermostat  will  be  under  ECO  heating/cooling  setting 

temperature with low fan speed. Press 

“ ” again for exit ECO mode 

 US (7 Days 4 Periods) programmable function: One week is divided into 7days with four periods in each 

day, 

each temperature can be set separately to meet the user’s different request in different time periods. 