5.2 Grounding
1.
5.2.1 Grounding the Charge Controller
1.
Open the charge controller. Remove the lid screws and the lid.
2.
Unscrew the metric-thread cable screw
connection's lock nut (A) and slide it over the PE
cable.
3.
Pull the PE cable through the cable screw
connection into the inside of the charge controller
and connect it to the "EARTH" connection terminal
(B).
4.
Tighten the lock nut of the cable screw connection.
L
Slot for communication interface
M
Socket for communication interface connection
N
M20 metric-thread cable screw connections for the battery, PV generator and PE
cables
O
M25 metric-thread cable screw connection for the signalling contact and the battery
temperature sensor cables
P
M25 metric-thread cable screw connection for communication cable
DANGER!
Risk of lethal electric shock.
The charge controller has the protection class I and must be properly grounded.
•
Ground the charge controller regardless of whether the battery and PV are
grounded.
Object
Description
Summary of Contents for SUNNY ISLAND SIC40-MPT
Page 2: ......
Page 6: ...SMA Solar Technology AG 6 SIC40 TEN081110 Technical Description...
Page 48: ...Contact SMA Solar Technology AG 48 SIC40 TEN081110 Technical Description...
Page 49: ...SMA Solar Technology AG Contact Technical Description SIC40 TEN081110 49...
Page 50: ...Contact SMA Solar Technology AG 50 SIC40 TEN081110 Technical Description...