10.3 Adjustable System Parameters
Inverter Settings
Battery Settings
Only change parameters marked with
(Stby)
, when the Sunny Island 3324/
4248 is in standby mode. Appropriately set operational data can take effect
as soon as the "Enter" key is pressed. Incorrect values in these parameters can
probably not be corrected quickly enough to avoid potential damage to your
system.
All parameters marked with a
(B)
can be set while the system is running.
All parameters can be set using a connected PC/laptop with the Sunny Data
Control software, a Sunny WebBox or a Sunny Boy Control.
No.
Name
Range/
unit
Default
Description
22-1
VacNominal
(B)
200 to 253 VAC
230
Setting of the inverter nominal output
voltage
No.
Name
Range/
unit
Default
Description
23-1
VdcBatNominal
(see section 11.4)
SI4248
42 to 48 VDC
48
Nominal battery voltage
SI3324
20 to 24 VDC
24
23-2
BatType
(see section 11.4)
VRLA
FLA
VRLA
The type of battery used in the system.
VRLA
= Gel/Absorbed Glass Mat
battery
FLA
= battery with liquid electrolyte
These parameters must be set when first
commissioning the system. After this, the
value can only be changed after you
have set the "23-5 New Battery"
parameter to the value "Reset". The Sunny
Island 3324/4248 will then again run
through the INIT phase.
23-3
AmpHoursBat
(see section 11.4)
100 to 6000 Ah
100
Battery capacity. These parameters must
be set when first commissioning the
system. After this, the value can only be
changed after you have set the "23-5
New Battery" parameter to the value
"Reset". The Sunny Island 3324/4248 will
then again run through the INIT phase.
23-4
AmpdcBatMax
(B)
SI4248
0 to 100 ADC
10
Maximum battery charging current
SI3324
0 to 140 ADC
10
Summary of Contents for Sunny Island 3324
Page 1: ...Sunny Island 3324 4248 User Manual User Manual Version 4 0 SI3324 4248 14 FE2406 TBE SI4248 ...
Page 2: ......
Page 6: ...SMA Technologie AG Page 6 SI3324 4248 14 FE2406 User Manual ...
Page 8: ...Notes on this Manual SMA Technologie AG Page 8 SI3324 4248 14 FE2406 User Manual ...
Page 14: ...The Sunny Island 3324 4248 SMA Technologie AG Page 14 SI3324 4248 14 FE2406 User Manual ...
Page 44: ...Automatic Frequency Adjustment SMA Technologie AG Page 44 SI3324 4248 14 FE2406 User Manual ...
Page 60: ...Troubleshooting Problem Solving SMA Technologie AG Page 60 SI3324 4248 14 FE2406 User Manual ...
Page 64: ...CE Declaration of Conformity SMA Technologie AG Page 64 SI3324 4248 14 FE2406 User Manual ...
Page 66: ...Contact SMA Technologie AG Page 66 SI3324 4248 14 FE2406 User Manual ...
Page 75: ...SMA Technologie AG User Manual SI3324 4248 14 FE2406 Seite 75 ...
Page 77: ......
Page 78: ......
Page 79: ......