8. 2 Grid connection data
Description
Short
descrip-
tion
Setting
SB 4200TL HC
SB 5000TL HC
Nominal output power
P
ACnom
4000 W
4600 W
Max. output power
P
ACmax
4200 W
5000 W
Nominal output current
I
ACnom
17.5A
20A
Harmonic distortion of output cur-
rent (at K
Ugrid
< 2 %, P
AC
> 0.5
P
ACnom
)
K
IAC
< 3 %
Operating range, grid voltage
U
AC
180 - 260 V AC
Germany: 198 - 260 V AC
b)
Operating range, grid frequency
f
AC
45.5 - 52.5 Hz
Germany: 47.55 - 50.2 Hz
Phase shift angle (based on the cur-
rent's fundamental frequency)
cos phi
1 (at nominal power output)
Overvoltage category
III
Test voltage (50 Hz)
1.65 kV (1 s routine testing / 5 s type
testing)
Test surge voltage
4 kV (1.2/50 ms)
(serial interface: 6 kV)
Internal consumption in night mode
0.25 W
b)
The Sunny Boy can temporarily feed power into the grid with a maximum output
voltage of 260 V. However, DIN VDE 0126-1-1 stipulates that the 10-minute
average must not exceed a voltage of 253 V. That means, if the grid voltage is
continuously 254 V (e.g.), the inverter disconnects itself from the grid. In this
case, contact the local grid operator for assistance.
DIN VDE 0126-1-1 only applies in Germany. See section 8.4. 3 "Country-spe-
cific Parameter Settings" (Page 43) for all other preset country values of your
inverter.
Summary of Contents for SB 4200TL HC
Page 2: ......
Page 10: ...Safety Instructions SMA Technologie AG Page 10 SBTLHCMS IEN080411 Installation Guide...
Page 30: ...Installation SMA Technologie AG Page 30 SBTLHCMS IEN080411 Installation Guide...
Page 44: ...Technical Data SMA Technologie AG Page 44 SBTLHCMS IEN080411 Installation Guide...
Page 60: ...The Communications Interface SMA Technologie AG Page 60 SBTLHCMS IEN080411 Installation Guide...
Page 63: ......