11 Activating and Deactivating the Backup System
11.1 Activation / Startup
Starting the Backup System via the Sunny Backup 2200
It is possible to start the Sunny Backup System without the Sunny Remote Control 1, but doing so will
limit the inverter to the factory default parameters (default values, see section 20.2 „Adjustable
System Parameters“ (142)).
Proceed as follows:
1. Insert the NH fuse into the BatFuse A.01(see „Inserting the NH Fuse“ (80)).
2. Push the DC start button on the Sunny Backup 2200.
The Sunny Backup 2200 turns on.
3. Push and hold the start / stop button on the Sunny Backup 2200.
During the startup process, the LED switches from yellow to green.
4. Release the start / stop button.
The inverter LED continuously glows green.
The Sunny Backup 2200 starts.
WARNING!
Risk if Sunny Backup System connections are incorrect.
Only qualified electricians are permitted to start up the device for the first time. Before
startup, check the Sunny Backup System S for
• correct electrical connections and proper device connection
• voltages and polarities
Information
The Sunny Backup System S can also be started without the Sunny Remote Control 1, but
then the device will only run with the factory default parameters.