VSL II DHW Settings
Use the following step to adjust parameter 3012, this parameter enables and controls
how DHW is controlled on the boiler. The table below lists all the possible settings for
parameter 3012. When setting up the boiler for use with the Slant/Fin DAWG parameter
3012 should be programmed to 2.
1.
Turn the main electrical supply Off;
2.
Press and hold, at the same time,
the RESET button and
button;
3.
Keeping the two buttons pressed,
turn the power on;
4.
Wait until the word “init” is displayed
or until display start to show the
3000 parameters;
5.
Let go of the RESET button and
after the
button;
6.
Parameters 3000 start to be
displayed;
7.
Press and release
and
buttons to scroll through the list of
parameters;
8.
Once the parameter has been selected,
it can be changed pressing the RESET
button (value start to blinking) and using
the and buttons
you
can
change the value;
9.
Press RESET button to save the
changed parameter;
10. Wait 10 seconds;
11. Turn the main electrical supply Off;
12. Turn the main electrical supply On to
leave the Factory menu.
3012
DHW mode
0 = no DHW
1 = DHW store with sensor
2 = DHW store with thermostat
3 = N/A
4 = N/A
5 = N/A