Slant/Fin GAS Modular Boilers Application Manual Download Page 1

HOT WATER/GAS 

Modular Boilers

APPLICATION GUIDE

Publication No. CG-10-HWG

Printed in the U.S.A. 1104

www.slantfin.com

Guidelines for the design, purchase and installation of Slant/Fin Caravan gas-fired, hot water modular boiler systems.

®

CONTENTS

Introduction  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Ratings and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
Recommended Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Optional factory supply and return headers  . . . . . . . . . . . . . .6
Boiler room design  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Boiler room air supply requirements  . . . . . . . . . . . . . . . . . . . .7
Typical layouts for gas-fired systems  . . . . . . . . . . . . . . . . . . .8
Venting a gas-fired system . . . . . . . . . . . . . . . . . . . . . . . . .9,10
Gas piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12

Controls  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13,14
Field wiring at modules  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
SC-3 system wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
SC-3 ladder wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
SC-9 space heating wiring  . . . . . . . . . . . . . . . . . . . . . . . . . .18
SC-9 space heating ladder wiring  . . . . . . . . . . . . . . . . . . . . .19
SC-9 space and domestic hot water wiring  . . . . . . . . . . . . .20
SC-9 space and domestic hot water ladder wiring  . . . . . . . .21
Caravan warranty  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Request for Caravan rating plate  . . . . . . . . . . . . . . . . . . .23,24

CODES AND STANDARDS

All Caravan installations must comply to local codes or, in the
absence of local codes, to the National Fuel Gas Code, ANSI,
Z223.1-latest edition.

In addition where required by the authority having jurisdiction, the
installation must conform to American Society of Mechanical
Engineers Safety Codes for controls and safety devices for 
automatically fired boilers, No. CSD-1. The installation must also
conform to the additional requirements of Slant/Fin Instruction Book
publication no. GG-100-40 latest edition.

All electrical wiring is to be done in accordance with the National
Electrical Code ANSI/NFPA No. 70-latest edition and all local electri-
cal codes. The unit must be electrically grounded if an external
power source is used.

In Canada, the installation must be in accordance with standards
CGA B149.1 and B149.2, installation codes for gas burning 
appliances and equipment and/or local codes. All electrical 
connections are to be made in accordance with Standard C.S.A.
C22.1 Canadian Electrical Code Part 1 and/or local codes.

Many state and local codes require intermittent ignition devices for
gas boilers. Please specify if necessary.

INTRODUCTION OF FRESH WATER

Introduction of excessive amounts of fresh water into a system can
cause scaling and leave deposits in the boiler and the surrounding
pipes. This will lead to inefficient boiler operation and breakdown.
Fresh water will enter the system as a result of hidden leaks such
as may occur in underground piping. Relief valves should be piped
to a location that shows visible signs of relief.

Process applications that use fresh water, require the use of heat
exchangers. Any process application that results in introduction of
fresh water into a boiler can cause scaling with deposits forming in
the boiler and surrounding piping. This will damage the boiler.
Introduction of fresh water from leaks will cause similar damage.

In some areas it may be necessary to use a feed water treatment to
control the corrosive makeup of the feed water. Check with the local
authority, to determine if the feed water will need a conditioning
treatment before being supplied to the boiler.

LOCAL CODE APPROVALS

New York City:

GGT and GGHT Caravan Modules -  MEA 283-93-E Vol. II
Slant/Fin vent damper NYS approval No. 8859

Pennsylvania:

Caravan boilers are approved in Pennsylvania by PA Cert. 174-BT-S

 

Summary of Contents for GAS Modular Boilers

Page 1: ...The unit must be electrically grounded if an external power source is used In Canada the installation must be in accordance with standards CGA B149 1 and B149 2 installation codes for gas burning appl...

Page 2: ......

Page 3: ...2275 78 1 82 4 4880 301 16 625 8 10 1323 32 253 16 115 16 21 2 3 GGHT 3375E 9 GG 375HEC 3375 2736 15860 2379 81 7 92 7 5490 301 16 595 8 10 1323 32 253 16 115 16 23 10 3 GGHT 3600E 9 GG 399HEC 3591 29...

Page 4: ...4 Design Data Max ASME Working Pressure 100 psi Power Requirements 120 volts 60 HZ 34 amps per module Figure 1 Gas Caravan dimensions and typical piping hot water models...

Page 5: ...r piping for variable circulation Figure 3 Supply and return piping locations Figure 4 Instantaneous tankless coil two temperature with recirculation Figure 5 Storage tank from tankless coil with reci...

Page 6: ...lief valve ASME unmounted Specify 30 50 or 100 psi Control header unmounted one per system Draft hoods unmounted OPTIONAL EQUIPMENT Hot water supply and return header assemblies Control panel with aut...

Page 7: ...opening near the floor below burner air inlet and one louvered opening near the ceiling above the highest draft regulator each opening with a minimum FREE air passage area of 1 square inch per 4000 B...

Page 8: ...8 Figure 8 Typical layouts for gas fired systems...

Page 9: ...uld be used where permitted for additional protection against adverse wind conditions and precipitation The National Board of Fire Underwriters recommend that the chimney should extend at least 3 feet...

Page 10: ...ation of this pipe in a typical appli cation Table 2a depicts the proper diameter Dim C of the connector rise depending upon its total length top of the draft hoods to the breeching above GG 200C 7 7...

Page 11: ...057 4 68 2 11 2 34 3 11 1 1 4 2 19 1 37 1 07 0 082 6 54 2 94 3 27 4 35 1 1 2 2 63 1 64 1 29 0 098 7 84 3 52 3 92 5 21 2 3 55 2 23 1 74 1 320 10 60 4 77 5 30 7 05 3 5 72 3 59 2 81 2 130 17 08 7 69 8 8...

Page 12: ...3 068 8 500 5 900 4 700 4 100 3 600 3 250 3 000 4 4 026 17 500 12 000 9 700 8 300 7 400 6 800 6 200 80 90 100 125 150 175 200 1 4 364 11 10 9 8 8 7 6 3 8 493 23 22 21 18 17 15 14 1 2 622 43 40 38 34 3...

Page 13: ...The view menu on the control includes error messages actual outdoor air temperature actual supply water temperature target supply water temperature and running time for each stage This control can be...

Page 14: ...Plastic tie straps Other Options include Immersion well for supply water sensor to be installed in control header supplied with Caravan High Limit manual reset and Immersion Well to be installed in co...

Page 15: ...15 FIELD WIRING AT MODULES...

Page 16: ...16 SC 3 SYSTEM WIRING DIAGRAM...

Page 17: ...17 SC 3 LADDER WIRING DIAGRAM...

Page 18: ...18 SC 9 SPACE HEATING WIRING DIAGRAM...

Page 19: ...19 SC 9 SPACE HEATING LADDER WIRING DIAGRAM...

Page 20: ...20 SC 9 SPACE AND DOMESTIC HOT WATER WIRING DIAGRAM...

Page 21: ...21 SC 9 SPACE AND DOMESTIC HOT WATER LADDER WIRING DIAGRAM...

Page 22: ...base jacket insulation combustion chamber tankless heater exhaust and air inlet piping burner enclosure mixing elbow gas and air orifice blower assem bly air filter and electrical and mechanical comp...

Page 23: ...CARAVAN SYSTEM RATING PLATE System rating plate format for Caravan modular boiler system System rating plates are available upon request using the form on the back cover...

Page 24: ...N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Each individual Caravan module is shipped with a rating plate bearing the model serial numb...

Reviews: