DOL 634 CE
Technical User Guide
61
16 Technical data
Electrical
Rated voltage
V AC
115*, 200* and 230/240 (*not speed controller)
Operating voltage
V AC
103.5-264
Frequency
Hz
50/60
Effect
W
75
Max. current consumption
A
0.7
Main module
Configurable main module.
Number 0-10 V:
-11 inputs and 2 outputs – or
- 9 inputs and 4 outputs – or
- 7 inputs and 6 outputs
Inputs
7 x 0-10 V DC input impedance 2.1 mOhm.
Outputs/power supply
2 x 15 V DC power /- 10 % max. 40 mA in total.
2 x motor supply 24 V DC +/- 20 % max. 0.4 A (in total for the entire
controller).
2 x supply for winch motor potentiometer 10 V DC max. 40 mA in total.
2 x 0-10 V DC Output impedance 100 Ohm.
Relays
12 x NO/NC potential free
Max. voltage/current at resistive load 250 V AC / 5 A AC.
Max. voltage/current at inductive load 250 V AC / 2A AC CosPhi 0.8.
1 x alarm relay NC, max. 24 V 2 A. Min. 12 V 10 mA (resistive load).
I/O module type 15
IO type 15, 10RL 8AI 8AO
No jumpers. Requires external resistors for use with e.g., water me-
ters. Comes with resistors.
Inputs
8 x 0-10 V DC input impedance 2.1 mOhm.
Pulsing Inputs
(e.g. water meter, energy
meter)
Minimum pulse length: 75 ms.
Minimum pulse interval: 75 ms.
Maximum frequency/pulse per sec.: 6 Hz.
Outputs/power supply
8 x 0-10 V DC output impedance 10 Ohm.
1 x motor supply 24V DC +/- 20%, 0.4 A.
Relays
10 x NO/NC potential free max.
Max. voltage/current at resistive load 250 V AC / 5 A AC.
Max. voltage/current at inductive load 250 V AC / 2A AC CosPhi 0.8.
I/O module type 3
IO type 3, 10RL 8AI 8AO
With jumpers for configuration of inputs.
Inputs
8 x 0-10 V DC input impedance 2.1 mOhm.
Pulsing Inputs
(e.g. water meter, energy
meter)
Minimum pulse length: 75 ms.
Minimum pulse interval: 75 ms.
Maximum frequency/pulse per sec.: 6 Hz.
Outputs/power supply
8 x 0-10 V DC output impedance 10 Ohm.
1 x motor supply 24V DC +/- 20% 0.4 A
Relays
10 x NO/NC potential free max.
Max. voltage/current at resistive load 250 V AC / 5 A AC.
Max. voltage/current at inductive load 250 V AC / 2A AC CosPhi 0.8.
Network