DOL 535 • DOL 539
Technical Manual
45
Check that the scale is connected correctly in relation to the lo-
cation intended by placing an object on the scale to make the
reading change.
Calibrate the scale according to the poultry scale manual. If you
connect the scale to a house controller with software version
6.6 or later, it should only be calibrated on the controller - not on
the scale itself. Also, see the section
5.2.1.15 Testing relay for 24-hour clock
Select the menu
Technical | Manual/auto.
Then select
Production | 24-hour clock
and activate
Manual mode
.
Activate the testing and check that the 24-hour clock is on.
Deactivate the testing and check that the 24-hour clock is off.
5.3 Testing network connection
If the controller is integrated in a network which can be accessed through the PC management program Far-
mOnline Explorer, the individual controllers must be visible in FarmOnline. Also see FarmOnline Explorer Tech-
nical Manual regarding testing of the network connection.