5 Testing
After installation of the system a thorough test must be carried out, to ensure that the system works as intended.
5.1 Testing basis components
5.1.1 Testing Alarm
Select
Alarm settings
.
Activate
Alarm test
to start testing.
Check that the alarm lamp is flashing.
Check that the alarm system alarms as intended.
Press
Acknowledge
to finish testing.
The test should then be made every week.
5.2 Testing optional components: Manual control
During testing, and in a service situation, the individual components connected to the climate or production con-
troller and be switched from automatic to manual control. Thus, you can easily test the optional components
such as winch motors, etc.
In the menu
Manual/auto
the house controller displays the components selected in the menu
Installation
.
Automatic control:
Normally the controller must be set to automatic control.
Manual mode:
During start up, or in a service situation, it may be convenient to control the individual functions
manually.
The component currently set for manual control are listed in the
menu
Technical | Manual/Auto | Manual mode
.
The manual control can also be deactivated here.
Select the function to be tested and test the components one at
a time.
A colored bar at the top of the page indicates that a component
is set for manual mode.