DOL 434 LPV
28
Technical Manual
The component currently set for manual control are listed in the
menu
Technical | Manual/Auto | Manual mode
.
The manual control can also be deactivated here.
Select the function to be tested and test the components one at
a time.
A colored bar at the top of the page indicates that a component
is set for manual mode.
After testing the components, you must set the function back to automatic control, so that the house
controller continues to operate as before.
I/O will remain in the setting that it was on at the moment the component was set to manual. This means that
operation continues when it is returned to automatic control.
5.2.1 Testing Climate Functions
5.2.1.1 Testing temperature simulation
This function is intended for the simulation of inside temperature changes when testing different functions. This
way it can e.g., be tested if the air inlets opens and closes, or if the stir fan switches on and off as expected.
To make sure the house controller is not left in manual temperature simulation mode the function has 2 timers
that will count down. The timer will start when the temperature setting is no longer being changed. The house
controller will start by giving an alarm (5 minutes) and then return to automatic control (15 minutes).
In the
Alarm settings | Climate | Sensors
menu the period before the alarm and the period before returning to
automatic regulation is set.
Select the menu
Technical | Manual/auto.
Then select
Climate | temperature sensor
and activate
Manual mode
.
Set the required temperature and check that the system responds as expected.
Each temperature sensor can be individually set.
5.2.1.2 Testing Air Intake and Air Outlet
The test is to show whether air inlet and air outlet can open and close completely.
Select the menu
Technical | Manual/auto.
Then select
Climate | Air inlets | Side Inlet 1
and activate
Manual mode
.