DOL 100 I/O Box
18
Technical User Guide
7 Technical data
DOL 100 I/O box
Electrical
Rated voltage
V AC
115, 200 and 230/240
Operating voltage
V AC
103.5-264
Frequency
Hz
50/60
Effect
W
75
Max. power consumption
A
0.7
IO type 15, 10RL 8AI 8AO
No jumpers. Requires external resistors for use with e.g., water me-
ters. Comes with resistors.
Inputs
8 x 0-10 V DC Input impedance 2.1 mOhm
Outputs
8 x 0-10 V DC Output impedance 10 Ohm
Relays
10 x NO/NC potential free max.
Max. voltage/current at resistive load 250Vac/5Aac
Max. voltage/current at inductive load 250Vac/2Aac
CAN bus
Protocol
CANopen in accordance with CiA301 and CiA401
Baud rate (non-adjustable)
Kbd
125
Max. cable length
m
400
Mechanical
Material
ABS
Cable knock-out holes
20 x M25 For metrical cable glands
Environment
Operating temperature
°C (°F)
-10 to +45 (+14 to 113)
Storage temperature
°C (°F)
-25 to +60 (-13 to +140)
Relative humidity, opera-
tion
% RH
0-80
Protection class
IP
54 (splash-proof)
It is assumed that the base surface is flat, i.e. ≤ there is a 1.5 mm dif-
ference in height, and the front panel screw is tightened to a minimum
of 1.5 Nm.
Shipment
Dimensions
H x W x D
mm
381 x 400 x 170
Packing dimensions
H x W x D
mm
425 x 555 x 195
Weight
g
5800
Shipping weight
g
6900