3.3 Wall inlet positioning
The positioning of the inlet in a wall depends on the layout of the building and the house layout. The positioning
may therefore only be made according to directions communicated by SKOV or representatives of the company.
The inlet must be placed horizontally in the wall. The inlet flap must be pointing into the house.
Place the insulation of the brickwork against the inlet all the way round (like in other categories of constructions).
This way you prevent a cold bridge along the side of the inlet from being formed.
The inlet is fixed on the inside wall by screws directly through the flange itself, see section
. In connection with brick and concrete walls, use mounting foam to fix the inlet, see section
3.4 Mounting inlet
3.4.1 Preparing hole in wall
Mark out the correct amount of holes according to measurements. Be aware of tolerance.
Distance to coil spring
Min. distance between holes
Min. distance to the wall on the
tensile side, see table below
1200 mm
950 mm
950 mm
220 mm
xxx mm
480 mm
280 mm
Distance to the ceiling
Positioning of actuator
Min. distance to the wall on the tensile side
[mm]
Min. 2100 mm
637 mm
637
700 mm
950 mm
1650
Min. 2100 mm
2100