Replacement Procedures
Service Manual
SERENE SC112N-A
Door Switch
The front door (electronic controller side) is fitted with a door switch (page 9).
The switch is located under the liner bottom below the front door and is
activated by a magnet at the bottom of the front door frame.
To replace the door switch
4. Detach the evaporator
shroud by undoing the
four fixing screws. Place
aside.
5. Withdraw the probe from
the evaporator coil and
trace the probe cable back
to the terminals at the rear
of the electronic controller.
Unplug from the controller.
6. Attach the new evaporator
probe cable to the
terminals at the rear of the
electronic controller and fit
the cable following the
same path as the original
probe cable. The probe is
located between the first
and second pipes, in
between the eighth and
ninth fins.
Probe entrance point
1. Isolate the chiller from the power supply, remove the shelves from the cabinet
and lock/secure the doors.
2. Separate the top cabinet assembly from the bottom refrigeration system (see
page 28).
3. Flip the cabinet assembly
over and place gently onto
its roof to access the door
switch.
4. Undo and replace the door switch.
5. Reassemble the cabinet and test.
Door switch