13
SERENE SC112N-A
Electronic Controller
Service Manual
Revision:
2.0
Application
SC112G
Controller Type
SKOPE S4 EVO
Controller Model & Revision
PZSKC0H002K (Rev 1.414)
SKOPE Part Number
ELZ11478-102
Setting
Unit
SET0
Min
Max
Parameter
102
CPS1017-102-SET0
Last revised on
27-Oct-2020
Full List
SET0
Access
Level
Range
Description
Electronic Controller Parameter Sheet
d/2
-
°C
F
-
-
Probe reading on 3rd Input (read only)
d10
-50.0
°C
C
-50.0
127
On demand defrost Start Temperature
d11
0
mins
C
0
60
On demand defrost: start delay
d12
127
°C
C
-50.0
127
Enabling defrost condition: Control probe threshold
d13
1
C
0
1
Evaporator Fans During Defrost (0 = Off 1 = ON)
d19
30
mins
C
0
200
No Downward Tendency Defrost - Start Delay (0 = function disabled)
d20
3
mins
C
1
< d19
No Downward Tendency Evaluation (Sample Time)
d21
3
C
0
5
Number of NDT defrosts before R.S.F. "Err" alarm (0 = function disabled)
d22
0.1
°C
C
0.0
5.0
No Downward Tendency Evaluation (Temperature Delta)
Alarm & Input Configuration Parameters
A0
2.0
°C
C
-20.0
20.0
Temperature Alarm Differential
AL
0.0
°C
C
-50.0
150
Low temperature alarm setpoint. (Relative if A0>0, Absolute (A0≤0)
AH
0.0
°C
C
-50.0
150
High temperature alarm setpoint. (Relative if A0>0, Absolute (A0≤0)
Ad
0
mins
C
0
199
Temperature alarm delay ( 0 = AL and AH alarms disabled)
A10
2
mins
C
0
10
Door Open Alarm delay (0 = door open alarm disabled)
A11
1
C
0
5
2nd Input Configuration
A12
3
C
0
16
Number of cA alarm events to trigger manual reset 'CA' alarm
A13
24
hrs
C
0
240
cA alarm counter reset delay
A14
60
mins
C
0
240
cA alarm reset delay
A15
1
C
0
1
Lights switched OFF when CHt, cA or CA alarm occurs
A18
1
C
0
1
Allow power cycle to reset CA alarm
A20
4
mins
C
A10
60
Faulty door/curtain switch E2 alarm delay
Ac
70.0
°C
C
-50.0
250
High condenser temperature alarm set point
AE
5.0
°C
C
0.1
20.0
High condenser temperature alarm differential
Acd
0
mins
C
0
250
High condenser temperature alarm delay
Acr
1
C
0
2
High condenser temperature alarm reset method
A21
2
C
0
5
3rd Input Configuration
Evaporator Fan Parameters
F0
3
secs
C
1
100
Loads Activation Delay
Fd0
20
mins
C
1
100
Fan DAY Duty Cycle : ON time
FdF
0
mins
C
0
100
Fan DAY Duty Cycle : OFF time
Fn0
25
mins
C
1
100
Fan NIGHT Duty Cycle : ON time
FnF
0
mins
C
0
100
Fan NIGHT Duty Cycle : OFF time
Other Parameters
H0
1
C
0
207
Supervisor Serial address
H01
1
C
0
1
Baud Rate (0 = 9600, 1 = 19200)
H02
2
C
0
2
Stop Bits
H03
0
C
0
2
Parity ( 0 = None, 1 = Odd, 2 = Even)
H2
1
C
0
3
Enable Keypad
H4
0
C
0
1
Disable buzzer (0 = Buzzer Enabled, 1 = Buzzer Disabled)
H5
102
F
0
199
ID code (read-only)
Warning
1. Only make program modifications with reference to relevant Operating Manual.
2. This programming sheet is exclusively for SKOPE refrigeration systems with its dedicated Carel controller.
3. Any alteration from this program may adversely affect the SKOPE Refrigeration System operation.
4. Specification may change without notice. Please check with SKOPE Customer Service for latest revision.