SKOPE ReFlex Chef Base Fridge
Troubleshooting and Diagnostics
Service Manual
Refrigeration System
Unlike in other SKOPE cabinets, the Chef Base refrigeration system is
integrated in to the cabinet and can not be easily removed.
The condensing unit can be easily accessed by removing the side panels.
The evaporator can only be removed by safely degassing the entire unit,
detaching the entire benchtop, and cutting or detaching the suction line.
A frost back check can be completed by unplugging cabinet, unplugging the
evaporator fan motor (white 4-pin plug) from the electrics box, and then
connecting the cabinet back to the power supply. The suction pipe at the
compressor should become cold and start to frost up if the unit is correctly
charged with refrigerant.