Replacement Procedures
Service Manual
Temperature
Probes
The electronic controller uses three temperature probes to gather data from
the refrigeration unit: the control, evaporator and condenser probes. The
probes connect into the rear of the electronic controller and exit from the rear
of the unit junction box to their locations.
Control Probe
For temperature control, temperature display and alarm temperatures, the
control probe is fitted to a bracket at the top of the cabinet interior ducting. It
plugs into the blue socket at the front RH side of the refrigeration unit.
To replace the control probe
1. Isolate the chiller from the power supply.
2. Remove the control
probe from the plastic
bracket.
3. Cut the failed probe from the probe cable.
4. Use wire cutters to remove the insulation from the probe cable wires and
from the replacement probe wires.
5. Insert the red wires of
each cable into a crimp.
Using a crimping tool,
crimp together.
6. Insert the other wires
into another crimp. Using
a crimping tool, crimp
together.
7. Refit the probe into the plastic bracket and reassemble.
Control probe
Plastic bracket