14
Electronic Controller
Service Manual
SKOPE BackBar X
Cold Climate
Protection
The chiller will enter cold climate protection (CCP) mode if the ambient
temperature becomes too cold. This happens if the control probe (at the
evaporator air out) detects the interior temperature below -1°C (parameter
St - CCt) for more than 30 minutes (parameter CCd). The lights will stay on
and cannot be switched off while the chiller is in CCP mode. The chiller will
return to Normal operation mode once the control probe reading raises to
parameter 1°C (parameter St) temperature.