Protection
Modbus
SKF Multilog On-Line System IMx-M
2 - 193
User Manual
Register "Digital Ch Status" Bit Definition
Table 2-39: Register "Digital ch status" bit definition (TRUE=1).
Register "Digital Ch Status" Bit Definition
Bit representation*
Description
(0x0000)
(No bit set)
Ch not configured.
0x0001
Ch enabled
0x0002
Ch alert
0x0004
Ch startup
0x0008
Ch danger
0x0040
Ch disarmed
0x0080
Slot disarmed
*
Important:
- Bit representation is in hexadecimal digits.
- Bit representation can be a combination of more than one condition.
Example: Bit representation of 0x004A is equal to 0x0002 Ch alert +
0x0008 Ch
0x0040 Ch disarmed
Refer to
Bit Representation of Combined Conditions
Register "Digital Ch Alarm Enable/Disable" Bit Definition
Table 2-40: Register "Digital ch Alarm enable/disable" bit definition (TRUE=1).
Register "Digital Ch Alarm Enable/Disable" Bit Definition
Bit representation*
Description
(0x0000)
(No bit set)
Alarm Disabled
0x0001
Alert Low
0x0002
Alert High
0x0004
Danger Low
0x0008
Danger High
*
Important:
- Bit representation is in hexadecimal digits.
- Bit representation can be a combination of more than one condition.