6. Installation
- 53 -
951-181-014-EN
Version 16
Electrical connection, Fig. 8
6.7 Electrical connection of ELNOR
motor
WARNING
Explosion hazard
Loss of pressure-resistant
encapsulation
After the assembly make sure to
correctly fasten the lid of the ter-
minal connection box again.
Use admitted cable only with the
specified diameters.
WARNING
Risk of explosion
Connect the product to the equi-
potential bonding of the superior
machine. Check the electrical
continuity before the initial
start-up.
For electrical connection proceed as
follows:
•
Loosen the 3 screws (1) and remove
the lid.
•
Unscrew the terminal insert (2a) of the
cable gland (2) to that extent that about
7 threads (3) will become visible.
•
Guide the cable through the cable
gland (2) into the terminal box.
Cable diameter
min.
6.5
mm
max. 11.7
mm
•
Connect supply lines in accordance with
the connection diagram (4) = red, (5) =
blue (6) = white (connection of thermal
circuit breaker).
2
1
2 a
2
Summary of Contents for 655-41261-1
Page 84: ...EN Annex 84 951 181 014 EN Version 16 Declaration of conformity of EDRN motor make SEW...
Page 85: ...15 EN Annex 85 951 181 014 EN Version 16 Declaration of conformity of DFR motor make SEW...
Page 86: ...EN Annex 86 951 181 014 EN Version 16 Declaration of conformity of BA AP80 motor make ELNOR...
Page 88: ...EN Annex 88 951 181 014 EN Version 16 Declaration of conformity of motor make CEMP...
Page 89: ...15 EN Annex 89 951 181 014 EN Version 16 Declaration of conformity of motor make CEMP...
Page 90: ...EN Annex 90 951 181 014 EN Version 16 Declaration of conformity of motor make CEMP...
Page 91: ...15 EN Annex 91 951 181 014 EN Version 16 Declaration of conformity of terminal box make Bartec...