background image

25

ENGLISH

as compressors or fans.

12. Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse environmental effects. The check 
shall also consider the effects of aging or continual vibration from sources such 
as compressors or fans.

13. Detection of 

fl

 ammable refrigerants

Under no circumstances shall potentially sources of ignition be used in the 
searching for or detection of refrigerant leaks. A halide torch (or any other de-
tector using a naked 

fl

 ame) shall not be used.

14.   Leak detection method

For systems containing 

fl

 ammable refrigerants, the following methods for de-

tecting leaks are acceptable:
Electronic leak detectors can be used for the detection of 

fl

 ammable  refrig-

erants, but the sensitivity may not be suf

fi

 cient or may require recalibration 

(the instrument calibration should be performed in a refrigerant-free environ-
ment) to ensure that the leak detector does not become a potential The ignition 
source, and applies to the measured refrigerant, the leak detector should be 
set to the lowest 

fl

 ammable concentration of the refrigerant (in percent), cali-

brated with the used refrigerant and adjusted to the appropriate gas concentra-
tion test range (max. 25%)
The leak detection 

fl

 uid is suitable for most refrigerants, but do not use oxygen-

ated solvents to prevent oxygen and refrigerant from reacting and corroding 
the copper pipeline If leakage is suspected, all open 

fl

 ames should be re-

moved from the site or extinguished If a leak occurs where welding is required, 
all refrigerant should be recovered, or the refrigerant should be completely 
isolated away from the leak (using shut-off valves). Before welding and during 
welding, use oxygen-free. Nitrogen (OFN) puri

fi

 es the entire system.

15.  Removal and evacuation

When performing maintenance or other operations on the refrigeration circuit, 
conventional procedures shall be used. However, for 

fl

 ammable refrigerants it 

is important that best practice is followed since 

fl

 ammability is a consideration. 

Summary of Contents for Dry Up SDHM-20L ECO

Page 1: ...SDHM 20L ECO DRY UP Dehumidifier GB INSTRUCTION MANUAL GR R290...

Page 2: ...GB ENGLISH 3 GR E 30...

Page 3: ...fore using and maintenance SYMBOLS FROM THE UNIT AND USER MANUAL This unit uses a flammable refrigerant gas If refrigerant gas leaks and comes in contact to fire or heating part it will be created har...

Page 4: ...ce or burn Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer Compliance with national gas regulations shall be observed Keep ventilatio...

Page 5: ...RMATION Avoid installation behind a door Use only with the supply voltage specified on the rating plate of the Dehumidifier Before installing cleaning and servicing turn off the power and unplug the u...

Page 6: ...ays remove plug from the mains supply before cleaning Switch off the appliance before changing its position Do not remove the power plug from the socket by pulling the cord grip the plug instead Alway...

Page 7: ...avy objects on the appliance Do not cover the intake or exhaust opening with cloths or tow els Do not drink or use the water drained from the unit Do not take the water tank out during operation Empty...

Page 8: ...the machine or injuries to persons or animals 4 In case of manipulation repairing or any modification of the machine made by unqualified persons or in case of improper use the guarantee will be autom...

Page 9: ...9 ENGLISH air outlet control panel float water tank cover water tank viewing window handle air inlet 3 in 1 filter washable dust filter OVERVIEW Front View Rear View...

Page 10: ...Formal dehyde levels are higher in new manufactured wood prod ucts such as flooring and furniture Formaldehyde can also be found in some fabrics Homes with smokers Tobacco smoke contains formalde hyde...

Page 11: ...l the unit on a flat horizontal surface CONTROL PANEL POWER Press the POWER button to turn the unit on or off LOCK Child Lock Keep the button pressed to lock or unlock all the keys Press and hold LOCK...

Page 12: ...ith high fan speed for any room humidity LOW DEHUMIDIFYING mode ECONOMY mode Press the MODE button twice to select this mode Here the unit always works with low fan speed for any room humidity FAN ONL...

Page 13: ...the key light above the Timer is on Setting of the timed startup Under the standby status of the machine the way to adjust the time is the same as that of the timed shutdown After the setting if ther...

Page 14: ...DISPLAY Auto Dehumidifying mode High Dehumidifying mode Low Dehumidifying Economy mode Fan Only mode Internal Drying mode Water Tank full Water Tank not placed correctly Room Humidity In Auto mode whe...

Page 15: ...mfort 4 The unit starts working in AUTO Dehumidifying mode with humidity set to 50 default value 5 Use the Mode button to change to other modes HIGH Dehumidifying LOW Dehumidifying or FAN Only 6 Use t...

Page 16: ...Empty the water only when the water tank is full Make sure that the assembly of the water tank cover and the water tank are correct Put one hand on the concave part on the bottom of water tank to car...

Page 17: ...ainage to avoid emptying the tank Note A 2m drainage pipe is provided with the unit Finf the continuous drainage port in the rear panel Connect the drainage pipe of cor rect lenght to the port Please...

Page 18: ...3 Clean the Washable Air Filter as described in the following section 4 When the unit will not be used for a long time use the Internal Drying Function to dry the interior to prevent mildew CLEANING...

Page 19: ...sn t oper ate Has the power cord been disconnected Plug the power cord into the outlet Is the Water Tank Full icon flashing This means that the tank is full or positioned incor rectly Empty the Water...

Page 20: ...y the appli ance is connected to Failure to comply may lead the supply authority to impose restrictions to connection Please consult your energy supply authority if the use of equipment exceeds 0 236...

Page 21: ...nition source When the portable air conditioner or dehumidifier is turned on the fan can work continuously stable under normal conditions to provide the minimum air volume of 100m3 h even when the com...

Page 22: ...or flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsically safe 5 Presence o...

Page 23: ...lled the ventilation machinery and outlets are operating adequately and are not obstructed if an indirect refrigerating circuit is being used the secondary circuit shall be checked for the presence of...

Page 24: ...ections terminals not made to original specification damage to seals etc Ensure that the apparatus is mounted securely Ensure that seals or sealing materials have not degraded to the point that they n...

Page 25: ...nsure that the leak detector does not become a potential The ignition source and applies to the measured refrigerant the leak detector should be set to the lowest flammable concentration of the refrig...

Page 26: ...m shall be vented down to atmospheric pressure to enable work to take place This operation is absolutely vital if brazing opera tions on the pipe work are to take place Ensure that the outlet for the...

Page 27: ...standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold extraction so that refrigerant can be removed from various parts of the system f Make sure that cyli...

Page 28: ...ng when applicable flammable refrigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and i...

Page 29: ...tly you will help prevent potential negative consequences for the environment and human health which could otherwise be caused by inappropriate waste handling of this product The recycling of material...

Page 30: ...30 T R290 R290 ODP GWP R290 R290...

Page 31: ...31 R290 4 m2...

Page 32: ...32...

Page 33: ...33 SINGER...

Page 34: ...34...

Page 35: ...35 1 service 2 SINGER SINGER SINGER...

Page 36: ...36 3 Singer 4 24...

Page 37: ...37 3 1...

Page 38: ...38 3 1 1 2 3 SDHM 20L ECO DRY UP 20L day 30 C 80 AC220 240V 50Hz 360W 2 2A 30 C 80 5 3L 180m h min max 44 47dB A R290 ecologic gas 95 g 239 x 388 x 598mm 14kg...

Page 39: ...39 POWER POWER TIMER POWE R HUMIDITY LOCK 3 SEC MODE 3 SEC TIMER POWE R HUMIDITY LOCK MODE 3 SEC 3 SEC...

Page 40: ...40 LOCK LOCK 2 LOCK 2 MODE MODE AUTO Auto 50 Humidity 5 High Speed 5 Low Speed 5 HIGH DEHUMIDIFYING MODE...

Page 41: ...41 LOW DEHUMIDIFYING ECONOMY mode MODE FAN ONLY MODE HUMIDITY INTERNAL DRYING MODE 2 MODE 2 Drying Power...

Page 42: ...42 TIMER X 0 24 Timer 1 24 24 1 Timer Timer 5 Timer Timer 5 Timer HUMIDITY 1 AUTO Humidity 40 70 5 40 45 70 65 40 2 FAN ONLY...

Page 43: ...43 LED AUTO Auto Humidity AUTO...

Page 44: ...44 1 2 Power 3 4 Auto 50 5 Mode 6 Humidity 7 Timer 8 Mode Drying 9 Lock LED...

Page 45: ...45 5 3 15...

Page 46: ...46 12 mm 2...

Page 47: ...47 1 2 3 4 Drying 40 C 3 1 3...

Page 48: ...48 2 C 2 C 30...

Page 49: ...49 drying 30 R290 0 236ohm 0 236 ohm...

Page 50: ...50 100m3 h...

Page 51: ...51 1 2 3 4...

Page 52: ...52 5 6 7 8...

Page 53: ...53 9...

Page 54: ...54 10 11...

Page 55: ...55 12 13 14 25 OFN...

Page 56: ...56 15 16...

Page 57: ...57 17 H...

Page 58: ...58 80 18 19...

Page 59: ...59...

Page 60: ...60 SSM EMC Directive 2014 30 EU LVC Low Voltage Directive 2014 35 EU ROHS Directive 2011 65 EU...

Page 61: ...61 NOTES...

Page 62: ...62 NOTES...

Page 63: ...63 NOTES...

Page 64: ...SSM S A 6 KIFISSOU STR 122 42 EGALEO ATHENS GREECE T 30 210 5386400 30 210 5138141 SSM A E 6 122 42 210 5386400 210 5138141 VELANIS APPLIANCES 62 104 43 T 210 5135874 210 5139517 www singer gr...

Reviews: